Section V
Battery Pack
006-0007129 10/12/2018
Rev B
46 of 60
UPS-1500 3-Phase Guide
www.synqor.com
Handling the Battery Pack
The operational temperature range of the battery pack is -20
°
C to +55
°
C (-4
°
F to +130
°
F). The
battery pack’s internal electronic circuitry will disable the battery if the cell temperatures are
outside this range. The SynQor UPS is equipped with internal battery heaters which activate
to keep the cells above 0
°
C in cold ambient temperatures.
Note: The storage temperature range of the battery pack is -40°C to +65°C (-40
°
F to +150
°
F).
Long term storage outside this temperature range will lead to a permanent reduction in the
battery’s energy storage capacity.
When the battery pack is not inserted into the UPS, the internal electronic circuitry disconnects
the battery from the pack’s power terminals. Nevertheless, care should be taken to avoid
making metal contact with (or between) any of these terminals.
The battery pack has its own aluminum chassis that protects its battery cells and internal
electronic circuitry from the environment when the pack is not inserted into the UPS. However,
care should be taken to ensure this chassis and the exposed power terminal strip are not
subjected to extreme mechanical shock or to excessive moisture.
UPS battery packs must be shipped per Federal DOT Regulations as a Class 9 Fully Regulated
Hazardous Material. The battery pack must not be installed in the UPS when being shipped,
and it must be packaged in the original SynQor Shipping Carton (including inner protective
inserts) which has been approved for shipping this product. The shipping carton must be
appropriately labeled per applicable Federal DOT Requirements. A UPS may be shipped using
standard shipping methods if it does not contain a battery pack. Please contact SynQor for
further assistance.
The battery pack should be disposed in accordance with applicable regulations of the locality
or returned to a factory-authorized Service Center.
Emergency response contact information for battery damage, leaks, smoke, or fires can be
found at the following link.
http://www.SynQor.com/UPS/documents/Contact.pdf
Please contact the SynQor factory for all other questions regarding the UPS battery pack.
CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
CAUTION: Do not open or mutilate batteries. Released electrolyte is harmful to the skin and
eyes. It may be toxic.
Always use the proper SynQor battery pack. See the battery replacement chart on page 45.