Section IV
Multiple Unit Configurations
006-0006452 MPC-1500 Operator Guide
Rev P
31 of 48
03/03/2021 www.synqor.com
Three MPC units with AC OUTPUTS Paralleled
For three MPC units having their outputs connected in standard parallel or redundant parallel,
the wiring diagram for the AC OUTPUT cables and the CONFIGURATION cable is shown below:
AC OUTPUT
AC OUTPUT
AC OUTPUT
L1 N
TO LOAD
PEGND
L1
N
PEGND
L1
N
PEGND
L1
N
PEGND
REAR PANEL
REAR PANEL
REAR PANEL
CONFIGURATION cable SYN-9315 or SYN-9343
When ordering, select the options “F: Floating” for standard parallel, or “R: Redundant” for
redundant parallel. Use CONFIGURATION cable SYN-9315 for standard parallel and SYN-9343 for
redundant parallel.
If the user is providing the AC OUTPUT cable, the cable sections shown above in either blue or in
red should have the following minimum wire size, depending on whether the AC OUTPUT of the
MPC units is 115 Vac or 230 Vac.
MPC AC Output Voltage
Blue Cable Section Minimum
Wire Size
Red Cable Section Minimum
Wire Size
115 Vac
#14 AWG (2.5 mm
2
)
#10 AWG (6mm
2
)
230 Vac
#16 AWG (1.5 mm
2
)
#12 AWG (4mm
2
)