Section V
Control Interface Details
006-0006452 MPC-1500 Operator Guide
Rev P
40 of 48
03/03/2021 www.synqor.com
The RS232 port provides readback of MPC’s state, as well as the configuration and control of the
MPC’s operation. The port can be used from a standard terminal interface, or from a custom
computer application.
Readback information that is available:
• AC Input Voltage
• AC Input Current
• AC Input Frequency
• DC Input Voltage
• AC Output Voltage
• AC Output Current
• AC Output Power
• AC Output Frequency
• DC2 Output Voltage
• DC2 Output Temperature
• DC Output Power
• Total Output Power
• External Switch Input Status
• Fan RPM
• Internal Temperatures
Parameters that are controllable through the interface:
• Output enable / disable
• Fan diagnostics
• Alarm enable / disable
For a detailed description of the terminal interface see the SynQor website at:
http://www.synqor.com/UPS/documents/UPS_User_Commands.pdf
Ethernet Interface
The Ethernet interface provides a web page based user interface for monitoring and control
of the MPC. The user can configure email alerts for MPC alarm conditions. The interface also
exposes an SNMP interface compliant to RFC-1628.
The Ethernet interface supports 10BASE-T and 100BASE-T standards. It utilizes a standard
RJ-45 connector, also allowing a metallic sealable circular military outer housing. The interface
supports auto-negotiation, polarity correction, and Auto-MDIX (detection and use of straight
through or cross-over cables).
IP address assignment can be done via DHCP or user entry of a static address. The interface also
supports a direct connection between the MPC and a host computer by including a DHCP server
internal to the MPC.
For a detailed description of the Ethernet port and SNMP implementation see the SynQor website
at:
http://www.synqor.com/ups/documents/UPS_Ethernet_SNMP_UG.pdf