Section III
Operation
006-0006715 10/31/18
Rev J
26 of 44
MPS-MPPS-4000 Guide
www.synqor.com
Programming The Output: MPPS Only
For the MPPS, the output voltage and output current can be programmed using the RS‑232
interface or using the web page interface. The MPPS cannot be programmed using the SNMP
interface.
Programming the Output From the Web Interface
• Ensure the web interface is configured properly. See the Ethernet/SNMP user guide for
details:
http://www.synqor.com/mps/documents/MPS_Ethernet_SNMP_UG.pdf
• Navigate to the “control” tab. The default address is http://169.254.1.1/control.htm
• In the “Configuration” section, enter the desired output voltage in mV click UPDATE. For
example “30000” corresponds to 30.000V output.
• In the “Configuration” section, enter the desired output current in amps click UPDATE. For
example, “50” corresponds to 50A.