1. Cause:
The salt quantity is too low or the entered parameter is
not correct.
Measure:
Empty the salt container and make a start-up as
described in the instructions manual chapter 5-4.
Malfunction message A3:
1. Cause:
The actuator ensuring the blending process is not
working.
Measure:
Contact the SYR customer service.
Malfunction message A4:
1. Cause:
The turbine is dirty or faulty.
Measure:
Clean or replace the turbine or contact the SYR
customer service.
2. Cause:
The Hall sensor is dirty or defective.
Measure:
Clean or replace the Hall sensor or contact the SYR
customer service.
Malfunction message A5:
Malfunction message A6:
2. Cause:
The water pressure is too low.
Measure:
Make sure that the dynamic pressure is at least 2 bar.
1. Cause:
There is no water in the salt container
Measure:
Fill with water and start up the device as described in