background image

D200-301-00

I56-4224-002

Pittway Tecnologica S.r.l. Via Caboto 19/3, 34147 TRIESTE, Italy

≤ 

M4

50-60 mm

107 mm

+

=

246 g

(66 g)

132 g

48 g

-30°C

40°C

B501RF

32 mm

104

 

mm

62 mm

DESCRIPTION

The 22051E-RF radio sensor is a battery operated RF device designed for 

use with the M200G-RF radio gateway. It contains a wireless transceiver 

and runs on an addressable fire system (using a compatible proprietary 

communication protocol).
It is an optical smoke sensor.

The sensor plugs into the B501RF wireless sensor base.

This  device  conforms  to  EN54-25  and  EN54-7.  It  complies  with  the 
requirements of 2014/53/EU for conformance with the RED directive.

SPECIFICATIONS

Supply Voltage:  

3.3 V Direct Current max.

Standby Current:  

@ 3V: 120 µA (typical in normal operating mode)

Red LED Current Max:   4mA

Re-sync time: 

35s (max time to normal RF communication from 

 

device power on)

Batteries: 

4 X Duracell Ultra123

Battery Life: 

4 years @ 25

o

C

Radio Frequency:   

865-870 MHz; 

RF output power:  

14dBm (max)

Range:  

500m (typ. in free air)

Relative Humidity: 

10% to 93% (non-condensing)

INSTALLATION

This equipment and any associated work must be installed in accordance 

with all relevant codes and regulations.

Figure 1 details the installation of the B501RF base.

Spacing between radio system devices must be a minimum of 1m

Figure 2 details attaching the sensor head to the base.

Anti-Tamper Features

The base includes a feature that, when activated, prevents removal of the 

sensor from the base without the use of a tool.  See Figures 3a and 3b for 

details on this. 

Head Removal Warning -

 An alert message is signalled to the CIE via the 

Gateway when a head is removed from its base.
Figure  4  details  the  battery  installation  and  the  location  of  the  rotary 

address switches.

Important

Batteries should only be installed at the time of commissioning

Warning

Using these battery products for long periods at temperatures below 

-20°C can reduce the battery life considerably (by up to 30% or more)

Observe the battery manufacturer’s precautions for use and 

requirements for disposa

l

SETTING THE ADDRESS

Set the loop address by turning the two rotary decade switches on the 

underside of the sensor (see figure 4), using a screwdriver to rotate the 

wheels to the desired address. The device will take one sensor address 

on the loop. Select a number between 01 and 159 (Note: The number of 

addresses available will be dependent on panel capability, check the panel 
documentation for information on this). 

PROGRAMMING

To load network parameters into the RF sensor, it is necessary to link the RF 

gateway and the RF sensor in a configuration operation. At commissioning 

time,  with  the  RF  network  devices  powered  on,  the  RF  gateway  will 

connect and programme them with network information as necessary. The 

RF sensor then synchronises with its other associated devices as the RF 

mesh network is created by the gateway. (For further information, see the 

Radio Programming and Commissioning Manual

 - ref. D200-306-00.)

NOTE:

 

Do not run more than one interface at a time to commission 

devices in an area.

22051E-RF

WIRELESS OPTICAL SMOKE SENSOR 

INSTALLATION AND MAINTENANCE INSTRUCTIONS

E N G L I S H

Figure 1: B501RF Mounting

Figure 2: Attaching Sensor Head to Base

Figure 3a: Activation of Tamper Resist Feature

PLASTIC LEVER

BREAK TAB AT DOTTED LINE BY 

TWISTING TOWARDS CENTRE OF 

BASE

Figure 3b: Removing Sensor Head From Base

USE A SMALL-BLADED SCREWDRIVER TO PUSH 

PLASTIC IN THE DIRECTION OF THE ARROW

LINE UP MARK ON 

SENSOR HEAD 

WITH BULGE ON 

BASE AND TURN 

CLOCKWISE

BULGE

MARK ON 

SENSOR HEAD

I 56- 4224- 002

Summary of Contents for 22051E-RF

Page 1: ...tion and the location of the rotary address switches Important Batteries should only be installed at the time of commissioning Warning Using these battery products for long periods at temperatures bel...

Page 2: ...varying types of smoke Consideration must be given to the environment when selecting and siting fire sensors Smoke sensors cannot last forever and we recommend replacement after 10 years Figure 5 Test...

Page 3: ...o illustrati l alloggiamento delle batterie e i selettori rotanti Importante Installare le batterie esclusivamente al momento della messa in esercizio Attenzione L uso di prodotti a batteria a tempera...

Page 4: ...io non durano indefinitamente Se ne consiglia la sostituzione dopo 10 anni Figura 5 Posizione del magnete per il test RIFERIMENTO SULLA BASE POSIZIONE DEL MAGNETE PER IL TEST Figura 6 Pulizia del sens...

Page 5: ...ores giratorios de direcci n Configurar la direcci n del lazo antes de instalar las bater as ver secci n siguiente Importante Instalar las pilas s lo en el momento de la puesta en funcionamiento Aviso...

Page 6: ...umo no duran para siempre Recomendamos sustituirlos cada 10 a os Figura 5 Posici n del im n de prueba MARCA EN LA BASE IM N DE PRUEBA Figura 6 Limpieza del sensor TAPA DEL SENSOR LENG ETAS PARA QUITAR...

Page 7: ...ehschalter Wichtig Die Batterien erst zum Zeitpunkt der Inbetriebnahme einsetzen Warnung Bei l ngerem Einsatz bei Temperaturen von unter 20 C kann sich die Lebensdauer der Batterien betr chtlich verri...

Page 8: ...beachten Rauchmelder halten nicht ewig Wir empfehlen einen Austausch nach 10 Jahren Abbildung 5 Position des Testmagneten MARKIERUNG AM MELDERSOCKEL TESTMAGNET Abbildung 6 Reinigung des Melders MELDER...

Page 9: ...orter aux Figures 3a et 3b Alerte Retrait T te Un message d alerte est signal la centrale via l interface lorsque la t te d un d tecteur est retir e de son socle Se reporter la Figure 4 pour plus de d...

Page 10: ...mpatible Les limitations du d tecteur sont les suivantes il ne d tecte pas le feu lorsque la fum e n atteint pas le d tecteur et peut r pondre de fa on diff rente suivant le type de fum e Une attentio...

Reviews: