D400-06-00                                                                                              1                                                                                              I56-286-05R

2412B, 2412THB, 2424, and 2424TH 
Direct Wire Photoelectronic 
Smoke Detectors

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

ww.systemsensor.com

Before Installing 

Please  thoroughly  read  the  System  Sensor  manual  A05-
1003, 

Applications  Guide  for  System  Smoke  Detectors

which  provides  detailed  information  on  detector  spacing, 
placement, zoning, wiring, and special applications. Copies 
of  this  manual  are  available  at  no  charge  from  System 
Sensor.  (For  installation  in  Canada,  refer  to  CAN/ULC-
S524,  Standard  for  the  Installation  of  Fire  Alarm  Systems 
and CEC Part 1, Sec. 32.)

General Description

System Sensor 2412 and 2424 photoelectronic smoke detec-
tors utilize state-of-the-art, optical sensing chambers. These 
detectors are designed to provide open area protection, and 
to be used with compatible UL-listed 4-wire control panels 
only.  The  2412  applies  to  12  volt  panels  and  operates  at 
12VDC, and the 2424 applies to 24 volt panels and operates 
at 24VDC. Operation and sensitivity can be tested in place. 
Models  2412TH  and  2424TH  have  the  same  specifications 
as models 2412 and 2424, but in addition feature a built-in 
fixed temperature (135°F) thermal detection unit.

Specifications

Diameter:                                       5.5 inches (14 cm)
Height:                                          3.19 inches (81 mm); Add 0.5 inches (1.3 cm) for thermal units
Weight:                                          0.7 lb (310 g)
Operating Temperature Range:        2412 and 2424 — 0°C to +49°C (32°F to 120°F)
                                                     2412TH and 2424TH — 0° to +38°C (32° to 100°F)
Operating Humidity Range:             10% to 93% Relative Humidity
Maximum Air Velocity:                   3000 Ft./Min. (15 M/S)
Latching Alarm:                             Reset by momentary power interruption.

Electrical Ratings                          2412                       2424

System Voltage:                                12                           24              

DC (4V Maximum Ripple)

Supply Voltage:                               11.3                         20              

VDC Minimum

                                                       17                           29              

VDC Maximum

Reset Voltage:                                   .73                          .8               

VDC Minimum

Standby Current:                             120                         120             

µ

A Maximum

Alarm Currents:                               35                         21.3             

mA Minimum

                                                       77                         40.6             

mA Maximum

The alarm and auxiliary relay operate within the specified voltage ratings.
Start-up Time:                                  34                           34              

S Maximum

EOL Relay:                                   A77-716                 A77-716
Reset Time:                                      0.3                         0.3
Relay Contacts – resistive or inductive (60% power factor) load:
Form A:                                         2.0A @ 30VAC/DC
Form C:*                                        0.6A @ 110VDC; 2.0A @ 30VDC
                                                     1.0A @ 125VAC; 2.0A @ 30VAC
(*For Canadian installations, relay contact rating is 2.0A @ 30VAC/DC)

An LED on each detector lights to provide a local alarm indi-
cation.  It  flashes  every  ten  seconds  indicating  that  power 
is  applied  to  the  detector.  The  LED  lights  continuously  in 
alarm. These detectors also have the latching alarm feature 
that resets only by a momentary power interruption.

Each detector contains one set of Form A contacts for con-
nection to the alarm-initiating circuit, and one set of Form C 
auxiliary contacts. Supervision of detector power is accom-
plished by installing a Power Supervisory End-of-Line Relay 
Module (A77-716 Series) at the end of the detector power 
loop. When power is applied to and through the detectors, 
the EOL Power Supervisory Module is energized. Its relay 
contacts close and provide a closed series circuit in the con-
trol panel’s alarm-initiating loop. A power failure or a break 
in  the  detector  power  loop  de-energizes  the  EOL  Module. 
The relay contacts open and trigger a trouble signal at the 
control panel.