background image

D100-96-00                                                                                               3                                                                                            I56-1800-07R

Figure 3b: Wiring Diagram, 4W-B and 4WT-B

AUX OR
SMOKE
POWER

IDC

4-WIRE
CONTROL
PANEL

+

+

4W-B or
4WT-B

(5

) COM

(4

) NO

(3

) – IN/OUT

(2

) + OUT

(1

) + IN

EOL
RELAY
(A77-716B)

EOL

RESISTOR

4W-B or
4WT-B

(5

) COM

(4

) NO

(3

) – IN/OUT

(2

) + OUT

(1

) + IN

S0134-00

Installation

WARNING

Remove power from alarm control unit or initiating device circuits 
before installing detectors.

NOTE:

 To install units so that corresponding LEDs are lined up, 

refer to the “Green LED” indicator on the base.
1.  Wire  the  mounting  base  screw  terminals  per  Figure  3a  or 

Figure 3b, as applicable.

2.  Place detector on the base and rotate clockwise. The detector 

will drop into the base and lock into place with a “click”.

3.  After  all  detectors  have  been  installed,  apply  power  to  the 

alarm control unit.

4.  Test each detector as described in 

Testing.

5.  Reset all the detectors at the alarm control unit.
6.  Notify the proper authorities that the system is in operation.

CAUTION

Dust  covers  are  an  effective  way  to  limit  the  entry  of  dust  into 
the  smoke  detector  sensing  chamber.  However,  they  may  not 
completely  prevent  airborne  dust  particles  from  entering  the 
detector.  Therefore,  System  Sensor  recommends  the  removal  of 
detectors before beginning construction or other dust producing 
activity. When returning the system to service, be sure to remove 
the dust covers from any detectors that were left in place during 
construction.

Testing

Detectors  must  be  tested  after  installation  and  following 
maintenance. 

NOTE:

  Before  testing,  notify  the  proper  authorities  that  mainte-

nance is being performed and the system will be temporarily out 
of service. Disable the zone or system undergoing maintenance to 
prevent any unwanted alarms.

Ensure proper wiring and power is applied. 

After power up, allow 

80 seconds for the detector to stabilize before testing.

Test i

3

 Series detectors as follows:

A. Test Switch

1.  An  opening  for  the  recessed  test  switch  is  located  on  the 

detector housing (See Figure 4).

2.  Insert a small screwdriver or allen wrench (0.18

 max.) into 

the test switch opening; push and hold.

3.  If  the  detector  is  within  the  listed  sensitivity  limits,  the 

detector’s red LED should light within five seconds.

Figure 4: Recessed Test Switch Opening and SENS-RDR 
Position

PUSH RECESSED
SWITCH WITH A 
0.18

 MAX.

DIAMETER TOOL

LED

RECESSED TEST SWITCH

POSITION SENS-RDR
AT AN ANGLE ON THE
OVAL AREA OR AT THE
CHAMBER OPENING
BY THE WORD “PAINT”

S0135-00

B.  Smoke Entry Test
  Hold a smoldering punk stick or cotton wick at the side of the 

detector and gently blow the smoke through the detector until 
it alarms.

C. Direct Heat Method (models 2WT-B and 4WT-B only)
  Using a 1000-1500 watt hair dryer, direct the heat toward either 

of the thermistors. Hold the heat source about 12 inches from 
the detector to avoid damage to the plastic. 

NOTE:

 For the above tests, the detector will reset only after the 

power source has been momentarily interrupted.

If  a  detector  fails  any  of  the  above  test  methods,  its  wiring 
should  be  checked  and  it  should  be  cleaned  as  outlined  in  the 

Maintenance

  section.  If  the  detector  still  fails,  it  should  be 

replaced.

Notify the proper authorities when the system is back in service.

Loop Verification (models 2W-B and 2WT-B only)

Loop  verification  is  provided  by  the  EZ  Walk  loop  test  feature. 
This feature is for use with i

3

 Series compatible control panels or 

the i

3

 Series 2W-MOD module only. The EZ Walk loop test verifies 

the initiating loop wiring and provides visual status indication at 
each detector.

1.  Ensure proper wiring and power is applied. Wait approxi-

mately six minutes before performing EZ Walk test.

2.  Place control panel or module in EZ Walk Test mode (refer 

to panel manufacturer’s manual or 2W-MOD manual D500-
46-00).

3.  Observe the LEDs on each detector:

Table 3: EZ Walk Test Detector Modes

Green LED

Red LED

Proper Operation

Double blink 5 sec

Out of Sensitivity

Double Blink 5 sec

Freeze Condition

Double Blink 10 sec

NOTE:

  The EZ Walk loop test must not be used instead of alarm 

testing.

Maintenance

NOTE:

 Before performing maintenance on the detector, notify the 

proper authorities that maintenance is being performed and the 
system  will  be  temporarily  out  of  service.  Disable  the  zone  or 
system undergoing maintenance to prevent any unwanted alarms. 

Power must be removed from the detector before performing 
maintenance of any kind.

Summary of Contents for 2W-B

Page 1: ...g replacement or a freeze condition 2WT B only at the control panel or module Installation of the 2W B 2WT B 4W B and 4WT B detectors is simplified by the use of a mounting base that may be pre wired to the system allowing the detector to be easily installed or removed The mounting base installation is further simplified by the incorporation of features compatible with drywall fasteners Two LEDs o...

Page 2: ...licable codes for specific information regarding the spacing and placement of smoke detectors CAUTION Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose Wiring Installation Guidelines All wiring must be installed in compliance with the National Electrical Code applicable state and local codes and any special require...

Page 3: ...r is within the listed sensitivity limits the detector s red LED should light within five seconds Figure 4 Recessed Test Switch Opening and SENS RDR Position PUSH RECESSED SWITCH WITH A 0 18 MAX DIAMETER TOOL LED RECESSED TEST SWITCH POSITION SENS RDR AT AN ANGLE ON THE OVAL AREA OR AT THE CHAMBER OPENING BY THE WORD PAINT S0135 00 B Smoke Entry Test Hold a smoldering punk stick or cotton wick at ...

Page 4: ...fication reset exceed 10 seconds use the maximum initial start up time Physical Specifications Heat Sensor Model 2WT B and 4WT B 135 F 57 2 C Freeze Trouble Model 2WT B and 4WT B 41 F 5 C Operating Temperature Range 2W B and 4W B 32 to 120 F 0 to 49 C 2WT B and 4WT B 32 to 100 F 0 to 37 8 C Operating Humidity Range 0 to 95 RH non condensing Storage Temperature Range 4 to 158 F 20 to 70 C Diameter ...

Reviews: