I56-4446-000
DB200-04-00
3
DEUTSCH
ESP
AÑOL
ENGLISH
IT
ALIANO
FRANÇAIS
A
K
A
K
EOL
Figure 5: Wiring
Diagram
V OUT (+)
V OUT (-)
ALARM COM
V IN (+)
VIN (-)
ALARM COM
ALARM NO
ALARM NO
Figure 7: Alignment Adjustment Locations
ALIGNMENT PROCEDURE
Warning: When power is initially applied to the detector, before the
alignment procedure has been completed, it may enter fault or alarm. To
prevent unwanted alarms, disable the zone prior to applying power.
The alignment of the 6500RE is divided into four steps: Coarse alignment,
fine adjustment, final gain adjustment, and final verification. It is necessary
for all four steps to be executed properly to ensure proper alignment of the
product.
Pre-Alignment Checklist
• Ensure that both the detector and reflector are mounted securely to
stable surfaces.
• Ensure that all wiring is correct, and that terminal blocks are fully
seated into their receptacles on the detector.
• Complete any wiring dressing to minimize movement to the detector
once the alignment procedure is completed.
• Ensure that the appropriate reflectors are used for the installed
distance.
• Ensure that the line of sight between the detector and reflector is clear
and that reflective objects are a minimum of 380mm from the line of
sight.
• Ensure that both the detector and reflector are mounted within their
operational parameters for off axis angles.
RESET
Terminals T5-1 and T5-2 provide connections used to complete the alarm circuit
. A 0 ohm shunt, or current limiting resistor should be fitted
depending on the application; these are supplied separately. Refer to the panel manufacturer for correct current limiting resistor values.
Terminals T5-3 and T5-4 are used to connect the optional Schottky diode when used with active end of line monitoring; refer to panel manufacturer for
details. Do not fit the diode unless it is specifically required otherwise the functioning of the system will be affected. Diode polarity must be observed for
correct operation.
EXTERNAL ALARM
LIMITING RESISTOR
OR SHUNT
POWER (+)
POWER (-)
INITIATING ZONE (+)
INITIATING ZONE (-)
• Disable the zone or system to prevent unwanted alarms before applying
power.
• Ensure power to the detector is “ON”.
FAULT COM
REMOTE FAULT OUTPUT
REMOTE ALARM OUTPUT
AUX (-)
TEST INPUT
RESET INPUT
Figure 6: Switch Locations
ALIGNMENT
POSITION
INDICATOR
OPTICS LOCK-DOWN
SCREWS X 2
CONTROL PANEL
ALIGNMENT
SENSITIVITY
TEST
OPTIONAL
SCHOTTKY DIODE
ALIGNMENT
MIRROR
FAULT NC
FAULT NC
FAULT COM
REMOTE FAULT OUTPUT
REMOTE ALARM OUTPUT
AUX (-)
TEST INPUT
RESET INPUT
V IN (+)
VIN (-)
ALARM COM
ALARM NO
V OUT (+)
V OUT (-)
ALARM COM
ALARM NO
Step 1. Coarse Alignment
See figures 6 and 7.
1. Ensure that both of the optics lock-down screws are loosened so that
the optics will move freely.
2. Looking through the alignment mirror at both the alignment gun sight
and reflector simultaneously, locate the position of the reflector in the
optical sight. Note that initially this step will require some practice. An
orange sticky label is supplied, which may be temporarily mounted next
to the reflector to aid initial location if the distance between the reflector
and the detector is large.
3. Once the reflector has been located, begin to adjust both the horizontal
and vertical alignment knobs so that the reflector becomes centred in
the alignment mirror. Caution: If the optics are incorrectly aligned in
this step, it will not be possible to proceed with the next step.
HORIZONTAL
ADJUSTMENT
ALIGNMENT
GUN SIGHT
VERTICAL
ADJUSTMENT
DIGITAL
SIGNAL
STRENGTH
READOUT
6500RE/6500RSE
6500RE/6500RSE
ZONE
EOL
DEVICE