background image

Important

Please Read Carefully And Save

This instruction manual contains important information about the instal-
lation and operation of waterflow detectors. Purchasers who install water-
flow detectors for use by others must leave this manual or a copy of it with
the user.
Read all instructions carefully before beginning. Follow only those instruc-
tions that apply to the model you are installing.

Use vane-type waterflow detectors in wet-pipe systems only. Do NOT use
them in dry pipe, deluge, or preaction systems. The sudden inrush of
water in such systems may break the vane or damage the mechanism.
Do not use in potentially explosive atmospheres. Do not allow unused
wires to remain exposed.

Principles Of Operation

Vane-type waterflow detectors mount to water-filled pipes in sprinkler sys-
tems. Waterflow in the pipe deflects a vane, which produces a switched
output–usually after a specified delay. All waterflow detectors have a con-
trolled delay mechanism. Delays do NOT accumulate; they reset if the
flow of water stops before the entire delay has elapsed. All switches actu-
ate when the water flow rate is 10 gallons per minute or greater, but will
not actuate if the flow rate is less than 4 gallons per minute. This System
Sensor installation manual covers the following waterflow detectors for
sprinkler/fire alarm applications.

Accuflow Models

Pipe Diameter

Pipe Schedules

AFD20      

2"

5 through 40

AFD25      

2-1/2"

7 through 40

AFD30-2      

3"

7 through 40

AFD35      

3-1/2"

7 through 40

AFD40      

4"

7 through 40

AFD50      

5"

7 through 40

AFD60      

6"

7 through 40

AFD80      

8"

10 through 40

Do NOT use any of the AFD models on copper pipe. The clamping forces
of the mounting bolts may collapse the pipe sufficiently to prevent the
detector from functioning properly.
Do NOT install steel or iron pipe sections in copper piping for mounting a
waterflow detector. Incompatibility between the dissimilar metals causes
bimetallic corrosion.

CAUTION

CAUTION

AFD Accuflow

Vane-type Waterflow Detector

with Solid State Time Retard

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Installation Guidelines

Before installing any waterflow alarm device, be thoroughly familiar with:

NFPA 72:

National Fire Alarm Code

NFPA 13:

Installation of Sprinkler Systems

NFPA 25:

Inspection, Testing and Maintenance of Sprinkler Systems

Other applicable NFPA standards, local codes, and the requirements of the
authority having jurisdiction
NOTE:

Installation methods other than those listed in this installation
manual may prevent the device from reporting the flow of water
in the event the associated sprinkler system is activated by a 
fire. System Sensor is not responsible for devices that have been 
improperly installed, tested, or maintained.

1. Mount the detector where there is adequate clearance for installation

and removal and a clear view of it for inspections. See Figure 1 for
mounting dimensions.

2. Locate detector 6 to 7 ft. above the floor to protect from potential damage.
3. On horizontal runs, position the detector on the top or side of the pipe.

Do not mount it upside down because condensation may collect in the
housing and impair the operation of the detector. For vertical flow
applications, mount the detector on pipe through which water flows
upward. Otherwise, the unit may not operate properly.

4. Mount the detector at least 6 inches from a fitting that changes the

direction of water flow and no less than 24 inches from a valve or
drain.

5. Be sure the direction-of-flow arrow matches the direction of flow in the

pipe.

Mounting Instructions

1. Drain the pipe.
2. Cut a hole at the desired location. Center the hole in the pipe, as

shown in Figure 2, and be sure the hole is perpendicular to the center
of the pipe. Before drilling, use a punch or scribe to mark the drill site
to prevent the bit from slipping. If the hole is off center, the vane will
bind against the inside wall of the pipe. Use a drill or hole saw to cut
a hole of the proper diameter. See Table 1 for hole size.

When drilling the hole with a hole saw, make certain that the center of the
cut does not remain in the pipe.

3. Remove burrs and sharp edges from the hole. Clean and remove all

scale and foreign matter from the inside of the pipe for one diameter
on each side of the hole to ensure free movement of the vane. Clean
the outside of the pipe to remove dirt, metal chips, and cutting lubri-
cant.

CAUTION

Specifications

Contact Ratings:

0.6 A @ 125 VAC; 2 A @ 30VDC

Triggering Threshold Bandwidth

(Flow Rate):

4 to 10 gpm

Static Pressure Rating:

450 PSI (Max) 2” – 8”

Dimensions, Installed:

3.5"H x 3.0"W x 6.7"D

Operating Temperature Range:

32°F to 120°F (0°C to 49°C)

Compatible Pipe:

See Accuflow models listed below

Shipping Weight:

4 to 7 lb., according to size.

Enclosure Rating:

NEMA Type 4

Voltage Range:

8.4–35 V (DC–FWR); 108–132 VAC

Power Requirements:

300µA at 12 and 24 V (DC–FWR) or
400µA at 120 VAC

U.S. Patent Number:

6,084,521; 3,845,259

Panel Compatibility:

The AFD waterflow indicators may receive power and operate on a two-
wire initiating zone of a fire alarm control panel. When determining com-
patibility of these devices, the standby operating voltage of the control
panel must be between 8.5 and 35 volts. In the standby mode, the AFD
draws a maximum current of 0.3 mA. In alarm, the AFD acts as a short
across the initiating zone (similar to a manual fire box). 

For two wire

conventional fire alarm control panels, not more than 5 waterflow
indicators may be connected to a single initiating zone.

The maximum

retard/reset time of the waterflow indicator plus the initiating zone shall
not exceed 90 seconds.

For two wire addressable control panels, the number of waterflow
indicators connected to the panel’s signaling line circuit shall be lim-
ited only by the circuit’s current capacity.

D770-29-00

1

I56-1570-003R

firealarmresources.com

Summary of Contents for AFD Accuflow

Page 1: ...quate clearance for installation and removal and a clear view of it for inspections See Figure 1 for mounting dimensions 2 Locate detector 6 to 7 ft above the floor to protect from potential damage 3 On horizontal runs position the detector on the top or side of the pipe Do not mount it upside down because condensation may collect in the housing and impair the operation of the detector For vertica...

Page 2: ...d clamp wire with screw in hole located between conduit entrance holes See Figure 10A page 4 5 If a second conduit entry is required remove the knockout plug using a flat blade screwdriver as shown on Figure 10B page 4 Strike sharply with a hammer to pierce the wall of the knockout plug Move to an adjacent wall section and repeat until the plug falls out Make sure that the waterflow detector is su...

Page 3: ... Module NOTE Consult FACP Manufacturers Compatibility Guide prior to instal lation Figure 4 4 Wire Addressable Wiring the AFD to an addressable panel using an auxiliary power supply for power Remove the Relay Wires from under the Power Terminals Connect these wires to the Addressable Module Figure 5 Wiring the AFD using 4 wires Aux Power from Panel Remove the Relay Wires from the Power Terminals C...

Page 4: ...n and suspected cause of failure The Company shall not be obligated to repair or replace units which are found to be defective because of dam age unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the Company be liable for any con sequential or incidental damages for breach of this or any other Warranty expressed or implied whatsoever even if the...

Reviews: