INSTALLATION AND MAINTENANCE INSTRUCTIONS
BEAM200A, BEAM200SA
Single-ended Reflected Type
Projected Beam Smoke Detector
D400-74-00
1
I56-2542-00R
Specifications
General
Range:
16 to 230 Feet (5 to 70m)
230 to 328 Feet (70 to 100m) using optional accessory BEAMLRK
Sensitivity:
25% to 50% Total Obscuration in 6 levels
Level 1 = 25%
Level 2 = 30%
Level 3 = 40%
Level 4 = 50%
Level 5 = 30% to 50% (Acclimate)
Level 6 = 40% to 50% (Acclimate)
Spacing:
30 to 60 Feet (9.1 to 18.3 m)
Response Time:
Alarm: 20 seconds typical
Trouble: 30 seconds typical
Trouble Conditions:
Beam Blockage (96% or More Obscuration)
Improper Initial Alignment
Self-compensation limit reached (service needed)
In Alignment mode
Test/Reset Features:
Integral Sensitivity Test Filter (BEAM200SA only, requires additional external power supply)
Sensitivity Filter (Incremental scale on reflector)
Local Alarm Test Switch
Local Alarm Reset Switch
Remote Test and Reset Switch Capability
(compatible with RTS451/RTS451KEYA)
Indicators:
Alarm:
Remote Output, Local LED (red)
Trouble:
Local LED (yellow)
Blink Pattern Indicates Trouble Diagnostics
Normal Operation:
Local LED (flashing green with communication)
Alignment Aids: Optical Gunsight (coarse adjustment)
00 to 99 Digital Display (fine adjustment)
Sensitivity:
Digital Display Readout in Percent Obscuration
Style 7 Operation:
On-board isolators provide style 7 operation.
(may be disabled via shunts on circuit board)
Environmental
Temperature:
–22°F to 131°F (–30°C to 55°C)
Note: for applications below 32°F (0°C) see Special Applications section of this manual.
Humidity:
10% to 93% RH Noncondensing
Mechanical
Shipping Weight:
Complete unit:
3.9 lbs. (1.77 kg)
Shipping Size:
15″ × 10.5″ × 6.5″ (381 mm × 267 mm × 165 mm)
Mounting:
Wall only without optional accessories
Wiring:
Plug-in Terminal Blocks (12 to 22AWG)
Adjustment Angle:
±10° Horizontal and Vertical
Paintable Trim Ring:
May be painted using enamel or acrylic type paints
6581 Kitimat Rd. Unit 6 Mississauga, Ontario L5N 3T5
1-800-SENSOR2, Télécopieur : 905-812-0772
WWW.SYSTEMSENSOR.CA