background image

mounted  with  the  transmitter/receiver  on  one  wall  and  the 
reflector  on  the  opposite  wall,  or  both  suspended  from  the 
ceiling,  or  any  wall/ceiling  combination.  In  the  case  of  the 
ceiling  mount,  the  distance  from  the  end  walls  should  not 
exceed  one-quarter  of  the  selected  spacing  (7.5  ft.  [2.3m] 
maximum if the spacing is 30 ft. [9.1m]). See Figure 2.

Figure 1. Spacing for smooth ceiling (side view):

C0254-00

Figure 2. Spacing for smooth ceiling (top view):

16 ft. (5m) Mini mum

328 ft. (100m)  Maximum

Tx/Rx

Reflector

S

Tx/Rx

Reflector

1/2 S Maximum

1/4 S

Max.

C0255-00

In  the  case  of  peaked  or  sloped  ceilings,  codes  may  specify 
spacing  of  detectors  by  using  horizontal  spacing  from  the 
peak of the roof or ceiling. Figures 3 and 4 show the spacing 
for both the shed type and peaked type sloped ceilings.

On  smooth  ceilings,  beam  smoke  detectors  should  gener-
ally  be  mounted  between  12  and  18  inches  (0.3  to  0.46m) 
from  the  ceiling.  In  many  cases,  however,  the  location  and 
sensitivity  of  the  detectors  shall  be  the  result  of  an  engi-
neering  evaluation  that  includes  the  following:  structural 
features,  size  and  shape  of  the  room  and  bays,  occupancy 

and  uses  of  the  area,  ceiling  height,  ceiling  shape,  surface 
and  obstructions,  ventilation,  ambient  environment,  burn-
ing  characteristics  of  the  combustible  materials  present, 
and  the  configuration  of  the  contents  in  the  area  to  be 
protected.

Figure 3. Sloped ceiling (shed type):

S

3 ft. (0.

9m)

Max.

S

1/2 S MAX.

Tx/Rx

Reflector

C0256-00

Figure 4. Sloped ceiling (peaked type):

1/2 S

S

S

1/2 S

3 ft. (0.9m)

Max.

3 ft. (0.9m

)

Max.

Mount Detector

Anywhere in This Area

Tx/Rx

Reflector

C0257-00

Mounting Locations

Beam  detectors  require  a  stable  mounting  surface  for 
proper  operation.  A  surface  that  moves,  shifts,  vibrates,  or 
warps  over  time  will  cause  false  alarm  or  trouble  condi-
tions.  Initial  selection  of  a  proper  mounting  surface  will 
eliminate false alarms and nuisance trouble signals.

Mount  the  detector  on  a  stable  mounting  surface,  such  as 
brick,  concrete,  a  sturdy  load-bearing  wall,  support  col-
umn,  structural  beam,  or  other  surface  that  is  not  expected 
to  experience  vibration  or  movement  over  time.  DO  NOT 

D400-74-00 

I56-2542-00R

Summary of Contents for BEAM200A

Page 1: ... Reset Switch Capability compatible with RTS451 RTS451KEYA Indicators Alarm Remote Output Local LED red Trouble Local LED yellow Blink Pattern Indicates Trouble Diagnostics Normal Operation Local LED flashing green with communication Alignment Aids Optical Gunsight coarse adjustment 00 to 99 Digital Display fine adjustment Sensitivity Digital Display Readout in Percent Obscuration Style 7 Operatio...

Page 2: ... a dual digi tal display that reads 00 to 99 This display is used to indi cate the signal strength of the beam in alignment mode and to indicate the sensitivity setting of the detector in percent obscuration when setting the sensitivity of the detector No additional equipment is needed for alignment of the beam Special Applications Due to the inherent capabilities of projected type beam detectors ...

Page 3: ...minal Blocks 3 Isolator Shunts 2 Instruction Manual 1 Orange Sticky Paper 1 Parts Diagram not to scale C0306 00 Detector Placement Thissectionofthemanualdiscussestheplacementofprojected beamdetectors Thoughthisinformationisbaseduponindustry expertise it is intended to be used only as a technical guide Always comply with the requirements of applicable codes and standards such as ULC S524 NFPA 72 Na...

Page 4: ...detectors shall be the result of an engi neering evaluation that includes the following structural features size and shape of the room and bays occupancy and uses of the area ceiling height ceiling shape surface and obstructions ventilation ambient environment burn ing characteristics of the combustible materials present and the configuration of the contents in the area to be protected Figure 3 Sl...

Page 5: ...ay be used to provide greater angular adjustment of the transmitter receiver unit If the perpen dicular plane of the reflector cannot be mounted within 10 of the optical line of sight then the multi mount kit can be used for the reflector See BEAMMMK instructions To aid in locating the reflector in the alignment mirror at long distances a bright orange sticky backed piece of paper is provided Remo...

Page 6: ...tector shall be no smaller than 22 AWG 1 0 mm2 For best system perfor mance all wiring should be twisted pair and installed in separate grounded conduit Do NOT mix fire system wiring in the same conduit as any other electrical wiring Shielded cable may be used to provide additional protection against electrical interference When installing the beam smoke detector in applications where the head uni...

Page 7: ...all wiring is correct Insure that terminal blocks are fully seated into their receptacles on the detector Complete any wiring dressing to minimize movement to the detector once the alignment procedure is com pleted Insure that the appropriate number of reflectors are used for the installed distance Distances between 230 328 Feet 70 100m require additional reflectors 4 total The BEAMLRK accessory s...

Page 8: ...the horizontal and vertical alignment knobs one at a time in the direction that increases the numeric signal level on the display Continue adjusting each axis one at a time going back and forth between them until a peak value is indicated If a value of 90 is achieved the detector will re adjust the electronic gain once again This will be indicated by a reading on the display When this happens halt...

Page 9: ...the high optical efficiency of the reflec tor the selection of the opaque material used to block the reflector is not critical Acceptable materials include but aren t limited to this manual or the cardboard packaging inserts See Figure 14 The detector should enter the fault condition indicated by the fault relay and the yellow LED see Appendix I If the detector does not enter the trouble condition...

Page 10: ...tinue to depress the sensitivity switch until the desired setting is achieved The digital display will turn off automatically if no further switch presses occur Sensitivity Setting Obscuration Display Reading Acceptable Distance Between Detector and Reflector Feet Acceptable Distance Between Detector and Reflector meters Level 1 25 25 16 4 to 120 5 0 to 37 2 Level 2 30 30 25 to 150 7 6 to 46 6 Lev...

Page 11: ...erial over the reflector lining it up with the graduated marks that are 10 less than the detec tor s setting in obscuration The detector should not alarm or fault Keep the material in place for a minimum of 1 minute 3 Place the blocking material over the reflector lining it up with the graduated marks that are 10 more than the detec tors setting in obscuration The detector should enter alarm withi...

Page 12: ...f NFPA72 and or ULC for peri odic maintenance and sensitivity verification of beam type detectors If the detector fails this test several steps should be taken to determine if the detector is faulty or simply needs to be re adjusted before returning the unit These steps include 1 Verify all wiring connections and appropriate power is applied to the detector 2 Verify that the optical line of sight ...

Page 13: ...detector and reflector for reflective objects in the pathway Trouble Beam Blockage Initial Response Off 4 Quick Blinks Blink Blink Off Beam Blockage Remove blockage Faulty unit Trouble Beam Blockage Long Term Response On 4 Quick Blinks Blink On Off Beam Blockage Remove blockage Faulty unit Initialization Power on Off Blink until complete Blink Blink Off Apply Power from discharged state Initializa...

Page 14: ...D400 74 00 14 I56 2542 00R Scale 1 1 D400 74 00 14 I56 2542 00R Appendix II Detector Drilling Template 4 345 6 190 ...

Page 15: ...Appendix III Reflector Drilling Template Scale 1 1 5 512 140mm 8 465 215mm D400 74 00 15 I56 2542 00R ...

Page 16: ...iscausedbytheCompany snegligenceorfault Somestates donotallowtheexclusionorlimitationofincidentalorconsequentialdamages so the above limitation or exclusion may not apply to you This Warranty gives you specific legal rights and you may also have other rights which vary from state to state Three Year Limited Warranty FCC Statement This device complies with part 15 of the FCC Rules Operation is subj...

Reviews: