background image

D200-39-00                                                                                              1                                                                                          I56-1977-004R

 3825 Ohio Avenue, St. Charles, Illinois 60174

800/736-7672, FAX: 630-377-6495

www.systemsensor.com

Before  installing  detectors,  please  thoroughly  read  the  NEMA 

Guide  for 

Proper  Use  of  Smoke  Detectors  in  Duct  Applications,

  which  provides 

detailed  information  on  detector  spacing,  placement,  zoning,  wiring, 
and  special  applications.  Copies  of  this  manual  are  available  from 
NEMA (National Electrical Manufacturers Association, 2101 L Street NW, 
Washington, DC 20037). NFPA Standards 72 and 90A should also be ref-
erenced for detailed information. 

NOTICE:

 This manual shall be left with the owner/user of this 

equipment.

IMPORTANT: 

This detector must be tested and maintained regularly fol-

lowing  NFPA  72  requirements.  The  detector  should  be  cleaned  at  least 
once a year.

General Description

An  HVAC  system  supplies  conditioned  air  to  virtually  every  area  of 
a  building.  Smoke  introduced  into  this  air  duct  system  is  distrib-
uted  to  the  entire  building.  Smoke  detectors  designed  for  use  in  air 
duct  systems  are  used  to  sense  the  presence  of  smoke  in  the  duct.

Contents of the Duct Smoke Detector Housing Kit

The DH200RPL Duct Smoke Detector consists of the following items
(See Figure 1.):

Figure 1. Exploded View Of Duct Smoke Detector Components:

NOTE:     

For ducts over 1

1

2

 feet (0.46m), longer sampling tubes must be ordered to complete the installation. They must be the correct length for the 

width of the duct where they will be installed. See Table 1 on page 3 to determine the sampling tube required for different duct widths.

Contents Of The Duct Smoke Detector

1.   Complete duct smoke detector assembly with 
      sensor
2.   Two #10 x 1

1

4

 sheet metal mounting screws

3.   Two sampling tube filters
4.   One test magnet
5.   Drilling template
6.   Two foam gaskets
7.   Four #6-self tapping mounting screws for the    
      sampling tube and optional exhaust tube  

 

      extension
8.   One sampling tube end cap
9.   One plastic sampling tube
10.  One #8 self-tapping screw for plastic sampling  
      tube   

NOTE: A detector sensor board DOES NOT need to 
be ordered separately.

INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS

The  DH200RPL  air  duct  smoke  detector  is  photoelectric  detector.  This 
smoke detection method combines with an efficient housing design that 
samples air passing through a duct and allows detection of a developing 
hazardous condition. When sufficient smoke is sensed, an alarm signal is 
initiated at the fire control panel monitoring the detector, and appropriate 
action can be taken to shut off fans, blowers and change over air handling 
systems, etc. This can prevent the distribution or it can isolate toxic smoke 
and fire gases throughout the areas served by the duct system.

Two LEDs on each detector may illuminate, if programmed by the system 
control panel, to provide a local alarm indication. There is also a remote 
alarm output for use with auxiliary devices. The DH200RPL has remote 
test capability with the RTS451/RTS451KEY Remote Test Station.

The  DH200RPL  incorporates  a  cover  tamper  feature.  When  the  cover  is 
removed for more than 20 minutes, the unit loses communication at the 
panel,  a  trouble  is  indicated  at  the  panel  and  the  alarm  relay  switches 
states  thereby  shutting  down  fans,  dampers  and  blowers.  In  the  case 
when the sensor is removed or when there is no power to the unit, only a 
trouble is indicated at the panel (alarm relay does not work any longer).

DH200RPL Intelligent Air Duct Smoke Detector
with Extended Air Speed Range

FOAM

GASKETS

SAMPLING TUBE

SAMPLING TUBE

FILTERS

DETECTOR

COVER

DETECTOR BOARD

CONDUIT HOLES

DETECTOR

HOUSING

TERMINAL STRIP

POWER BOARD

COVER MOUNTING

SCREWS

Summary of Contents for DH200RPL

Page 1: ... filters 4 One test magnet 5 Drilling template 6 Two foam gaskets 7 Four 6 self tapping mounting screws for the sampling tube and optional exhaust tube extension 8 One sampling tube end cap 9 One plastic sampling tube 10 One 8 self tapping screw for plastic sampling tube NOTE A detector sensor board DOES NOT need to be ordered separately INSTALLATION AND MAINTENANCE INSTRUCTIONS The DH200RPL air d...

Page 2: ...cause an interruption of power The system safeguards should be discussed with your local fire protection specialist WARNING This device will not sense smoke unless the ventilation system is operat ing WARNING In order to function properly this detector must be installed according to the instructions Do not exceed the electrical or ambient specifications or the detector will not function properly T...

Page 3: ...ange into the housing bushing that meets the air flow first Position the tube so that the arrow points into the air flow Secure the tube flange to the housing bushing with two 6 self tapping screws 3 From inside the duct couple the other sections of the sampling tube to the section already installed using the 1 2 inch conduit fittings sup plied Make sure that the holes on both of the sampling tube...

Page 4: ... 004R NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch 75mm floor flange available at most plumb ing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connector mounting technique drill a 1 inch to 11 4 inch 25 to 32mm hole where the flange will be used ...

Page 5: ...ERLY 9 1 4 Air Flow Test using Dwyer Series 607 Differential Pressure Transmitter Verify the air speed of the duct using an anemometer Air speed must be at least 100 FPM Wire the Dwyer transmitter as shown in Figure 8 Connect the leads of the meter to either side of the 1000Ω resistor Allow unit to warm up for 15 seconds With both HIGH and LOW pressure ports open to ambient air measure and record ...

Page 6: ...ion Trouble If the detector LEDs do not flash then the de tector lacks power check wiring panel pro gramming or power sup ply the detector board is missing replace or the unit is defec tive return for repair Additionally if the cover is removed for more than 20 minutes the LEDs of the detector will not flash Test The trouble condition can be caused intentionally to veri fy correct operation of the...

Page 7: ... 2 Lift the photo chamber in the same fashion Vacuum the screen and cover Use clean compressed air to loosen and blow out any remaining debris Replacement screens p n S08 39 01 are available 3 Vacuum photo chamber then use clean compressed air to blow area clean 4 Replace the chamber by pressing it onto the base Press the screen into place It should fit tightly on the chamber 10 Board Replacement ...

Page 8: ... encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help System Sensor warrants its enclosed air...

Reviews: