background image

Install the inlet tube as follows:

1. Drill a 3/4-inch hole in the duct directly opposite the

hole already drilled for the inlet tube.

2. Slide the inlet tube with the flange into the centermost

housing bushing. Position the tube so that the arrows
point into the air flow. Secure the tube flange to the
housing bushing with two #6 self-tapping screws.

3. From inside the duct, couple the other section of the in-

let tube to the section already installed using the 1/2-
inch conduit fitting supplied. Make sure that the holes
on both of the air inlet tubes are lined up and facing into
the air flow.

4. Trim the end of the tube protruding through the duct so

that 1 to 2 inches of the tube extend outside the duct.
Plug this end with the end plug and tape closed any
holes in the protruding section of the tube. Be sure to
seal the duct when the tube protrudes.

NOTE:

An alternate method to using the ST-10 is to use
two ST-5 inlet tubes. Remove the flange from one
of the tubes and install as described above. After
the installation, use electrical tape to close off
some of the sampling holes so that there is a total
of 10 to 12 holes spaced as evenly as possible
across the width of the duct.

Air currents inside the duct may cause excessive vibration,
especially when the longer sampling tubes are used. In
these cases a 3 inch floor flange (available at most plumb-
ing supply stores) may be used to fasten the sampling tube
to the other side of the duct. When using the flange/con-
nector mounting technique, drill a 1 inch to 1-1/4-inch hole
where the flange will be used.

[5.4.3] Modifications Of Inlet Sampling Tubes

There may be applications where duct widths are not what
is specified for the installation. In such cases, it is permis-
sible to modify an inlet sampling tube that is longer than
necessary to span the duct width.

Use a 0.193-inch diameter (#11) drill and add the appropri-
ate number of holes so that the total number of holes ex-
posed to the air flow in the duct is 10 to 12. Space the
additional holes as evenly as possible over the length of the
tube.

[5.5] Field Wiring

Wiring Installation Guidelines

All wiring must be installed in compliance with the Na-
tional Electrical Code and the local codes having jurisdic-
tion. Proper wire gauges should be used. The conductors
used to connect smoke detectors to control panels and ac-
cessory devices should be color-coded to reduce the likeli-
hood of wiring errors. Improper connections can prevent a
system from responding properly in the event of a fire.

For signal wiring, (the wiring between interconnected de-
tectors or from detectors to auxiliary devices), it is usually
recommended that single-conductor wire be no smaller
than 18 gauge. The duct detector terminals accommodate
wire sizes up to 14 gauge. The last foot of conduit should
be flexible steel conduit (available in electrical supply
houses), which facilitates installation and puts less strain
on the conduit holes in the housing. Solid conduit connec-
tions may be used, if desired.

Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel manufacturer’s specifications for the total
loop resistance allowed for the particular model control
panel being used before wiring the detector loop.

Wiring Instructions

The DH400ACDC detectors are designed for easy wiring.
The housing provides a terminal strip with clamping plates.
Wiring connections are made by stripping about 3/8-inch
of insulation from the end of the wire, sliding the bare end
under the plate, and tightening the clamping plate screw.

The DH400ACDC duct detector is designed to operate from
24 VDC, 24 VAC, 120 VAC, or 240 VAC.

The detector may be wired for interconnection to UL listed
control panels, or for stand alone service per NFPA 90A.
Refer to the wiring diagrams of Figures 6, 7, and 8 to select
the appropriate circuit for your application.

D400-13-00

5

I56-555-08

Summary of Contents for DH400ACDC

Page 1: ... Photo Head Exploded View 11 Fig 14 Ion Head Exploded View 11 1 General Description An HVAC system supplies conditioned air to virtually every area of a building Smoke introduced into this air duct sys tem will be distributed to the entire building Smoke detec tors designed for use in air duct systems are used to sense the presence of smoke in the duct Model DH400ACDC Air Duct Smoke Detectors are ...

Page 2: ...m safeguards should be discussed with your local fire protection specialist WARNING This device does not sense smoke unless the ventilation system is operating CAUTION For this detector to function properly it MUST be installed according to the instructions in this manual Furthermore the detector MUST be protected from the elements and op erated within ALL electrical and environmental specifica ti...

Page 3: ... TUBE EXTENSION BUSHING DUCT DETECTOR HOUSING O RINGS MOUNTING SCREWS INLET SAMPLING TUBE BUSHING A78 2045 00 Figure 3 Speed nut mounting location HOLE B HOLE A DUCT WALL SPEED NUT 78 2046 00 5 4 Install The Inlet The inlet tube shown in Figure 4 is identified by a series of air inlet holes on the tube This tube must be purchased separately Order the correct length as specified in Table 1 for widt...

Page 4: ...tector inlet sampling tube INLET TUBE END PLUG AIR HOLES ARROWS MUST FACE INTO AIR FLOW AIR FLOW DIRECTION FLANGE A78 2047 00 AIR FLOW DIRECTION DUCT DETECTOR HOUSING DOTS INDICATE POSITION OF SAMPLING TUBE HOLES AIR FLOW DIRECTION DUCT DETECTOR HOUSING INLET TUBE EXHAUST TUBE AIR FLOW DIRECTION INLET TUBE EXHAUST TUBE INLET TUBE EXHAUST TUBE DUCT DETECTOR HOUSING AIR FLOW DIRECTION EXHAUST TUBE I...

Page 5: ...l and add the appropri ate number of holes so that the total number of holes ex posed to the air flow in the duct is 10 to 12 Space the additional holes as evenly as possible over the length of the tube 5 5 Field Wiring Wiring Installation Guidelines All wiring must be installed in compliance with the Na tional Electrical Code and the local codes having jurisdic tion Proper wire gauges should be u...

Page 6: ...WN OPEN IN STANDBY CONTACTS CLOSE IN ALARM 8 9 ALARM INITIATION CONTACTS CONTACTS SHOWN OPEN IN STANDBY CONTACTS CLOSE IN ALARM ALARM INITIATION LOOP UL LISTED CONTROL PANEL FIRST DETECTOR IN THE LOOP DH400ACDC LAST DETECTOR IN THE LOOP DH400ACDC EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPL...

Page 7: ...ICES REFER TO MANUFACTURER S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER TROUBLE CONTACT RATING 0 3A 32 VAC DC POWER INPUTS ACCEPT 24 VDC 24 VAC 50 60 HZ 120 VAC 50 60 HZ OR 220 240 VAC 50 60 HZ CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR ALARM AUXILIARY CONTACT RATINGS 10A 30 VDC 10A 250 VAC 500mA MINIMUM 24 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS ALARM INITIATI...

Page 8: ...AY BE USED SUCH THAT THE GIVEN CURRENT LOADS TOTAL RESET TEST NOTE WHEN INITIATING AN ALARM THE RTS451 RTS451KEY REQUIRES 95mA MAXIMUM IN PRE ALARM AND 103mA MAXIMUM IN ALARM NOMINAL STANDBY CURRENT IS 0mA ALARM CURRENT IS 10mA MAXIMUM WHEN TEST MAGNET IS REMOVED 100mA OR LESS IN THE STANDBY STATE 150mA OR LESS IN THE ALARM STATE A78 2354 00 5 7 Perform Detector Check 1 Perform the STANDBY AND TRO...

Page 9: ...1 Detector head removal TEST LOCATOR TEST MAGNET PAINTED SIDE TOWARD HOUSING DUCT HOUSING DETECTOR HEAD RESET LOCATOR TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TWIST CLOCKWISE TO INSTALL DETECTOR HEAD A78 2138 00 A78 2139 00 Trouble If the detector LEDs do not blink or if the APA451 Power LED is not illuminated the detec tor lacks power check wiring panel or power supply the head is missing in...

Page 10: ... can be turned counterclock wise DETECTOR HEAD TEST COIL Figure 12 RTS451 RTS451KEY test coil installation A78 1994 02 4 Carefully reinsert the detector head into the duct hous ing and wait 50 seconds for power up Do not hold the swirl chamber to twist the detector head 5 Insert the NO ALARM end of the test card into the test slot see Figure 13 and slide it counterclockwise until it stops The dete...

Page 11: ...screens RS14 are available 4 Brush or vacuum the inside of the cover The cover may then be blown out with clean compressed air 5 Vacuum the sensing chamber before using clean com pressed air to loosen and blow out any remaining debris 6 Press the screen back into the cover 7 Replace the detector cover onto the sensing chamber Rotate it clockwise to lock it into place REMOVABLE HEAD COVER CLEANABLE...

Page 12: ... sems plates accept wire sizes of 14 gauge or smaller The screws can withstand 10 in lbs of tightening torque without damage Accessories MOD400R Sensitivity Test Module RA400Z Remote Annunciator RTS451 RTS451KEY Remote Test Station test reset switch with alarm LED PA400 Piezo Sounder APA451 Annunciator with piezo alarm power LEDs CRT400 Cover Removal Tool Ion only F36 05 00 Replacement Air Filter ...

Page 13: ...MINAL STANDBY CURRENT IS 0mA ALARM CURRENT IS 10 mA MAXIMUM WHEN TEST MAGNET IS REMOVED Three Year Limited Warranty System Sensor warrants its enclosed air duct smoke detector to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture System Sensor makes no other express warranty for this air duct smoke detector No agent r...

Page 14: ...NOTES D400 13 00 14 I56 555 08 ...

Page 15: ...NOTES D400 13 00 15 I56 555 08 ...

Page 16: ..._______________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ___________________________ _______ __________ _______ ____________ ____...

Reviews: