FAAST 7100X
INSTALLATION AND MAINTENANCE INSTRUCTIONS
© Pertronic Industries Ltd
1
FAAST XS (7100X) Installation Guide Iss 1.0, 201606
TABLE OF CONTENTS
SPECIFICATIONS:
Electrical Characteristics:
External Supply Voltage
18 – 30V
DC
Remote Reset Time
External monitor must be pulled low for a minimum of 100msec.
Power Reset
10 secs (FAAST 7200BPI); 1 sec (FAAST 7100X)
Average Operating Current
Fan Hi: 200mA; Fan Med: 151mA; Fan Lo: 120mA @ 24V
DC
Alarm Current
Fan Hi: 230mA; Fan Med: 172mA; Fan Lo: 142mA @ 24V
DC
Additional Current Requirements
LCD ON: 10mA; EtherNet Enabled: 20mA; Serial ModBus Enabled: 20mA
Average Loop Driver Operating Current: 700µA
Loop Driver Voltage Range:
15 – 32V
DC
Relay Contact Ratings
3.0A @ 30V
DC
, 0.5A @ 125V
AC
Environmental Ratings:
Operating Temperature
0°C to 38°C
(32°F to 100°F) Factory Tested to 55°C (131°F)
Sampled Air Temperature
-20°C to 60°C
(-4°F to 140°F)
Humidity
10 to 95% (non-condensing)
Hazardous Environments
Suitable for use in Class I, Division 2, Groups A, B, C & D,
or Non-Hazardous locations only
IP Rating
IP30
Coverage Area
600m
2
(6,450ft
2
)
Ambient Air Movement
0 - 1,219.2m/min.
(0 - 4,000 ft/min.)
Mechanical Characteristics:
Exterior Dimensions
280 x 230 x 160
H x W x Dmm
Cable Access
3 x 25.4mm cable entry holes on top, back and left of unit.
Wire Gauge
2.0mm (12 AWG) max to 0.5mm (24 AWG) min.
Shipping Weight
4kg, includes packing material
Nett Weight
3kg
Pipe Network Size:
Up to 600m
2
Maximum single pipe length
54.8m
External pipe diameter
25mm
Internal pipe diameter
15 - 21mm
Document Colour Code Key:
(refer to Page 28)
SS Blue: Document Headers
Black:
general instructions/information applying to 7200BPI Device
Blue:
important settings to be configured on each 7200BPI
A. Specifications:………………………………… 1
Introduction:…………………………….......….…2
Description:………………………………........… 2
Installation:.……………………..……………...... 2
Wiring........…………….……………..……....….. 3
User Interface:.…………………………....…...... 5
Modes of Operation:……..…………………....... 9
Logs........……………………………..…..…......11
External Monitor / Reset………………........… 11
Connections…………………………………..... 11
Pipe Network……….………………………...… 11
Web Server……………….…………………..… 11
Smoke Tests………………….………………... 11
Maintenance……....................................……. 11
B. Connection Using PipeIQ..….…….…….….. 12
PipeIQ Quick Start Instructions...............……. 12
C. Configuring FAAST XS in PipeIQ..….….….. 12
Configuration………….…………….........……. 12
Design……………........…………….........……. 17
D. Configuring Pertronic Fire Alarm Panels.... 20
Analogue Addressable F100/F120….……..... 20
Conventional F16e/F4/F100LR-3…………..... 20
Conventional F16e/F16/F4/F100LR………..... 20
E. Monitoring FAAST XS using PipeIQ.…….… 21
Views…………………..…………….........……. 21
F. System Testing and Commissioning….….. 22
Required Items………………….….........……. 22
Commissioning and HandOver…..........……. 22
Commission Testing………….….....……… 22
Inspection of Installation…………..…..….. 22
Power Up/Configuration…………………. 22
Commissioning Tests…………………….…23
Signalling…………………………………... 24
System Check………………………..…… 24
System Handover……………………….... 24
G. Flow Rate Conversion Table………………... 25
Glossary………………………….….........……. 26
H. FAAST System Validation Form….………... 27