FAAST 7100X 
INSTALLATION AND MAINTENANCE INSTRUCTIONS

  

© Pertronic Industries Ltd  

FAAST XS (7100X) Installation Guide  Iss 1.0, 201606 

 

TABLE OF CONTENTS 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

SPECIFICATIONS: 

Electrical Characteristics: 

External Supply Voltage  

18 – 30V

DC

 

Remote Reset Time  

External monitor must be pulled low for a minimum of 100msec. 

Power Reset  

10 secs (FAAST 7200BPI); 1 sec (FAAST 7100X) 

Average Operating Current  

Fan Hi: 200mA; Fan Med: 151mA; Fan Lo: 120mA @ 24V

DC

 

Alarm Current 

Fan Hi: 230mA; Fan Med: 172mA; Fan Lo: 142mA @ 24V

DC 

Additional Current Requirements 

LCD ON: 10mA; EtherNet Enabled: 20mA; Serial ModBus Enabled: 20mA 

Average Loop Driver Operating Current:   700µA 
Loop Driver Voltage Range:  

15 – 32V

DC

 

Relay Contact Ratings  

3.0A @ 30V

DC

, 0.5A @ 125V

AC

 

Environmental Ratings: 

Operating Temperature  

0°C to 38°C 

(32°F to 100°F)   Factory Tested to 55°C (131°F) 

Sampled Air Temperature  

-20°C to 60°C 

(-4°F to 140°F) 

Humidity  

10 to 95% (non-condensing) 

Hazardous Environments 

Suitable for use in Class I, Division 2, Groups A, B, C & D, 

 

or Non-Hazardous locations only 

IP Rating  

IP30 

Coverage Area  

600m

2

 (6,450ft

2

Ambient Air Movement  

0 - 1,219.2m/min. 

(0 - 4,000 ft/min.) 

Mechanical Characteristics: 

Exterior Dimensions  

280 x 230 x 160 

H x W x Dmm 

Cable Access  

3 x 25.4mm cable entry holes on top, back and left of unit. 

Wire Gauge  

2.0mm (12 AWG) max to 0.5mm (24 AWG) min. 

Shipping Weight  

4kg, includes packing material 

Nett Weight  

3kg 

Pipe Network Size:  

Up to 600m

2

 

 

Maximum single pipe length  

54.8m 

 

External pipe diameter  

25mm 

 

Internal pipe diameter  

15 - 21mm

Document Colour Code Key: 

(refer to Page 28)

 

SS Blue: Document Headers 

Black: 

general instructions/information applying to 7200BPI Device 

Blue: 

important settings to be configured on each 7200BPI

 

 

 

A. Specifications:…………………………………  1 

Introduction:…………………………….......….…2 
Description:………………………………........… 2 
Installation:.……………………..……………...... 2 
Wiring........…………….……………..……....….. 3 
User Interface:.…………………………....…...... 5 
Modes of Operation:……..…………………....... 9
Logs........……………………………..…..…......11 
External Monitor / Reset………………........… 11 
Connections…………………………………..... 11 
Pipe Network……….………………………...… 11 
Web Server……………….…………………..… 11 
Smoke Tests………………….………………... 11 
Maintenance……....................................……. 11 

 

B. Connection Using PipeIQ..….…….…….….. 12 

PipeIQ Quick Start Instructions...............……. 12 

 

C. Configuring FAAST XS in PipeIQ..….….….. 12 

Configuration………….…………….........……. 12 
Design……………........…………….........……. 17 

 

D. Configuring Pertronic Fire Alarm Panels.... 20 

Analogue Addressable F100/F120….……..... 20 
Conventional F16e/F4/F100LR-3…………..... 20 
Conventional F16e/F16/F4/F100LR………..... 20 

 
E. Monitoring FAAST XS using PipeIQ.…….… 21 

Views…………………..…………….........……. 21 

 

F. System Testing and Commissioning….….. 22 

Required Items………………….….........……. 22 
Commissioning and HandOver…..........…….  22 

Commission Testing………….….....……… 22 
Inspection of Installation…………..…..….. 22 
Power Up/Configuration………………….  22 
Commissioning Tests…………………….…23
Signalling…………………………………... 24 
System Check………………………..……  24 
System Handover……………………….... 24 

 

G. Flow Rate Conversion Table………………... 25 

Glossary………………………….….........……. 26 
 

H. FAAST System Validation Form….………... 27 

Summary of Contents for FAAST 7100X

Page 1: ...x W x Dmm Cable Access 3 x 25 4mm cable entry holes on top back and left of unit Wire Gauge 2 0mm 12 AWG max to 0 5mm 24 AWG min Shipping Weight 4kg includes packing material Nett Weight 3kg Pipe Network Size Up to 600m2 Maximum single pipe length 54 8m External pipe diameter 25mm Internal pipe diameter 15 21mm Document Colour Code Key refer to Page 28 SS Blue Document Headers Black general instru...

Page 2: ...are The e system r flow and e sent upon nitored at th technology nuisance im uisance alarm 20 5 obs on local cod o 20 5 obs elays ring air flow sensi s sensor tren auto adjustm ation and diag olate condition e indicator FAAST 710 INSTALLA 2 c Th loc Pi Th pa tha the Th wi Ph En the Se Th wa mo Fo po loc 1 2 3 4 5 ance to a etection tem for ations ntrolled oles to e user relays splayed terface disp...

Page 3: ... Wiring Before working on the FAAST system notify all required authorities that the system will be temporarily out of service Make sure all power is removed from the system before opening the unit All wiring must be in accordance with local codes Power Cables Use the power ratings of the unit to determine the required wire sizes for each connection Use the power ratings of the connected products t...

Page 4: ...Table 1b for the proper electrical connections to the unit and Figure 4b for typical connection for monitoring a Stand Alone FAAST system at a Fire Alarm Control Panel FACP Figure 4b 7100X to FACP Wiring Diagram FAAST 7100X System Powering The following procedure describes how to initially power up the FAAST system 1 Unplug the unit s power connector to the unit before turning the power ON 2 Turn ...

Page 5: ...ng the PipeIQ software Each alarm level controls a set of Form C relay contacts When an alarm level threshold has been crossed the corresponding Alarm LED illuminates and the relay activates after the Alarm Delay period has elapsed These alarm thresholds and associated relay outputs can be configured for either latching or non latching operation Each Alarm output has a configurable delay from 0 to...

Page 6: ... Select or enter highlighted item on the LCD screen Cancel Back or Escape from current menu selection Fault Display The FAAST XS user interface displays faults in two ways using amber LEDs on the right side of the user interface and on the LCD screen The four Fault LEDs are Figure 9 Fault Display If the General Fault LED is ON the fault condition is shown on the LCD Display under the Active Faults...

Page 7: ...e mode When selected the device requests confirmation Use the scroll keys to select Cancel or OK and then select key to confirm the selection 3 4 Reset IP The Reset IP function sets the device into Reset IP mode When selected the device requests confirmation Use the scroll keys to select Cancel or OK and then select key to confirm the selection 3 5 Test Mode The Test Mode function sets the device ...

Page 8: ...t detail for the currently displayed event Use the scroll keys to advance up or down the events 6 Message Log The Message Log history can be viewed through the LCD screen The Message Log screen displays the message number currently being displayed the total number of messages available and the message Use the scroll keys to advance up or down the messages 7 LCD Setting The LCD settings menu allows...

Page 9: ...y activates The Alarm thresholds and their associated relay outputs are configurable for latching or non latching operation For each Alarm level there is a configurable delay from 0 to 60 seconds Configurable thresholds for each alarm level are Audible Indicator Configuration The FAAST XS has an integrated audible indicator which provides the option to include a supplementary audible indication fo...

Page 10: ...n Disable mode Day Night Weekend Mode Day Night Weekend mode is the default setting which may be used if Acclimate mode is not desired This allows the device to have separate threshold levels for simple Day Night and Weekend mode Times can be configured if desired for entering and exiting the Day and Night time operation It transitions to Weekend mode on Saturday and Sunday The device has an inter...

Page 11: ...he FAAST XS system is a network capable device that is compatible with standard Ethernet networking equipment Connectivity is provided by an on board RJ45 connector located inside the wiring cabinet Once initial setup is complete the Ethernet connection provides optional remote access monitoring and email notification through the unit s Web server and SMTP client USB Connection A USB port located ...

Page 12: ...and verify the performance of pipe network solutions draw and view pipe designs in 3D configure the design parameters to suit local fire codes and standards generate Pipe Layouts BOMs Configuration and Event Log Reports test relays and alarms perform smoke test and fans speed test retrieve and view logs in graph and tabular form control test and monitor FAAST aspirating detectors A comprehensive H...

Page 13: ...assword default is password g Connect Connection to the FAAST XS a Open PipeIQ v2 or greater on the PC by default PipeIQ opens in Configuration mode b Open a project file mdf to continue use one of the following methods i open an existing project configuration mdf file for the FAAST XS or ii start a New Config and add a FAAST detector of the type to be installed or being maintained save this Confi...

Page 14: ... is correct simply select the arrow to download the PC time to the detector Time Format select either 12 Hour or 24 Hour format Trend Log select the Frequency for logging the detector functions to the Trend Log note that as the frequency increases the duration of the Log reduces Capacity Frequency Duration of Log the rate is limited to a range of 1 to 60 minute or 1 to 24 hour periods depending on...

Page 15: ...ect Port iv Device Connection select an IP Address automatically via DHCP or use a Static IP Address Obtain an IP Address automatically via DHCP contact the site IT department to obtain the information required to connect to the site s ethernet Use a Static IP Address IP Address Default 192 168 1 10 Subnet Mask Default 255 255 255 0 Default Gateway Default 192 168 1 1 DNS Server Primary and Second...

Page 16: ...guage 16 languages are available for the graphics display default is English English iv Sounder Fault Tone select Off Pulsed or Continuous Alarm Tone select Off Pulsed or Continuous f ModBus i ModBus determines the ModBus operating mode TCP ethernet based RS485 serial based RTU or ASCII based as required ii Passcode sets the Passcode to unlock the buttons on the device user interface default Passc...

Page 17: ... the Calculation icon i select Set Hole Sensitivity ii set the Target Sensitivity for each of the activation levels Alert Fire 1 and Fire2 the Target Sensitivity represents the sensitivity at the Sampling Point and equates to the sensitivity of a point detector eg an OPT detector typical Target Sensitivity levels may be press the arrow to convert each Target Sensitivity to Threshold then OK to acc...

Page 18: ...ints then CUSTOM first review the Sensitivity settings used by VEWFD EWFD or SFD to identify appropriate settings for the system being configured then apply settings suitable to the CUSTOM constraints v acknowledge any advisory notices then verify all Settings meet the Constraints verify Flow Balance should be 0 70 select Auto Balance to maximise Flow Balance and manually adjust Hole Diameters if ...

Page 19: ...els can be sequentially updated to match the Day values simply by pressing the arrow or alternately Night and Weekend settings can be customised vii Select the device from the tree right click and select Device Information record the following details in Section H FAAST XS System Validation Form a Fan Speed RPM b Flow Velocity Chamber c Flow Velocity Inlet d Flow Base Chamber e Flow Base Inlet Flo...

Page 20: ...E 2 relay may activate the Fire relay ALERT terminate with a 10K EOL resistor to Normalise the circuit switch a 470R resistor to activate as a Smoke Alarm FIRE 1 and ALERT may be combined on a single circuit on the F16e provided the circuit is configured for Residential mode and the 7100X FIRE 1 relay switches the 180R resistor Heat Alarm and the ALERT switches the 470R resistor Smoke Alarm DEFECT...

Page 21: ... control Log View Live Events Monitor Live Events as they occur Search for Live Events Produce Reports in pdf doc or xls format Clear Live Events Stored Events Retrieve Stored Events Search for Stored Events produce Reports in pdf doc or xls format Clear Stored Events Messages facility to add notes for future reference and or advice to colleagues regarding issues or tasks performed or required Add...

Page 22: ...2010 and the ASD Sensitivity Alarm thresholds are correctly set to ensure that the sensitivity of individual holes meets the minimum performance requirements for individual points Note that this may require reference to the approval compliance notes for the particular ASD system and should also take into account any potential automatic adjustments of the Sensitivity Threshold settings which may oc...

Page 23: ...e design documentation engineering specifications but must not exceed 90 seconds NZS4512 2010 Where an Alarm indication is used it does not generally include any Alarm delays which are temporarily set to zero for the measurement of Transport Time Measured Transport Time should be compared to the predicted design Transport Time c Fault Detection Simulate the following faults on the detector and che...

Page 24: ...nd detector locations and shall be deemed part of the system handover All the collated documentation along with a signed certificate should be issued to the customer Sensitivity Class vs Detection Requirements Table 7 Sensitivity Class vs Detection Requirements Class EN54 20 Class A Class B Class C Very High Sensitivity Enhanced Sensitivity Normal Sensitivity TF2x End of Test Condition 1 15 obs m ...

Page 25: ...1 54 1 55 32 2 33 1 59 1 60 33 3 34 1 64 1 65 34 3 35 1 68 1 70 35 3 36 1 73 1 75 36 4 37 1 78 1 80 37 4 38 1 83 1 85 38 4 39 1 88 1 90 39 5 40 1 92 1 95 40 5 41 1 97 2 00 41 6 42 2 02 2 05 42 6 43 2 07 2 10 43 6 44 2 12 2 15 44 7 45 2 17 2 20 45 7 46 2 21 2 25 46 8 47 2 26 2 30 47 8 48 2 31 2 35 48 8 49 2 36 2 40 49 9 50 2 41 2 45 50 9 51 2 45 2 50 52 0 52 2 50 2 55 53 0 53 2 55 2 60 54 0 54 2 60...

Page 26: ...er the date of manufacture In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other warranty expressed or implied whatsoever even if the loss or damage is caused by the Company s negligence or fault Some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitation or exclusion may not apply ...

Page 27: ...Inlet m s General Model Number 7100X Serial Number Identification Number Loop Address Contact Person Customer Name Facility Name Facility Location Device Location Site Address Daylight Saving Starts On Last Sunday September 02 00 Ends On First Sunday April 03 00 Time Format 12 Hour 24 Hour Time Saved 60 min Trend Log Frequency Mins Hrs Sensor Night Mode Start Time End Time Alarm Fault Relay Latchi...

Page 28: ... Sec Fan Speed High Medium Low User Interface Button Activation Passcode Lock Out Configuration Menus Device Configuration LCD Controls Functions Sounder Fault Tone Off Pulsed Continuous Alarm Tone Off Pulsed Continuous Graphics Display Language English ModBus TCP Passcode Address RS485 RTU ASCII Baud Rate Data Bits Stop Bits Parity System Tests Transport Time Actual Predicted Air Flow Block the E...

Reviews: