background image

D100-67-00

1

I56-1148-04

DH100 Air Duct Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read the System Sensor 

Guide for Proper

Use of Smoke Detectors in Duct Applications 

(I56-473)

,

which provides detailed information on detector spacing,
placement, zoning, wiring, and special applications. Cop-
ies of this manual are available from System Sensor. NFPA
Standards 72 and 90A should also be referenced for de-
tailed information.

NOTICE:

 This manual should be left with the owner/user

of this equipment.

IMPORTANT: 

This detector must be tested and maintained

regularly following NFPA 72 requirements. The detector
should be cleaned at least once a year.

Table of Contents

Page

[1] General Description

 1

[2] Limitations of Duct Smoke Detectors

1

[3] Exploded View of Duct Smoke Detector Components 2
[4] Contents of the Duct Smoke Detector Kit

2

[5] Installation Sequence

2

[6] Duct Smoke Detector Maintenance and Test Procedures 5
[7] Detector Cleaning Procedures

7

[8] Board Replacement

7

[9] Specifications

8

Warranty

8

[1] General Description

An HVAC system supplies conditioned air to virtually every
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense
the presence of smoke in the duct.

Model DH100 Air Duct Smoke Detectors are supplied as a
photoelectronic model. This smoke detection method is
combined with an efficient housing design that samples air
passing through a duct and allows detection of a develop-
ing hazardous condition. When sufficient smoke is sensed,
an alarm signal is initiated at the fire control panel monitor-
ing the detector, and appropriate action can be taken to
shut off fans, blowers, change over air handling systems,
etc. These actions can facilitate the management of toxic
smoke and fire gases throughout the areas served by the
duct system.

DH100 detectors are designed to operate with 12 or 24
VDC UL listed compatible 2-wire control panels. Alarm
current must be limited to 100mA or less by the control
panel. Auxiliary relay contacts for control purposes are
not available for use with the DH100. Control must ini-
tiate from the control panel.

For testing, the alarm can be enabled by a magnet acti-
vated test switch or by the optional remote test station.
The duct smoke detector latches into alarm state when
an alarm occurs. A green LED flashes to indicate power,
a red LED signals local alarm indication, and optional
accessories offer a variety of annunciation capabilities.

The DH100 can be reset by a momentary power interrup-
tion, the reset button on the front cover, the control panel,
or remote reset accessory.

[2] Limitations Of Duct Smoke Detectors

WARNING

The National Fire Protection Association has established
that DUCT DETECTORS MUST NOT BE USED AS A SUB-
STITUTE FOR OPEN AREA DETECTOR PROTECTION as a
means of providing life safety. Nor are they a substitute for
early warning in a building’s regular fire detection system.

System Sensor supports this position and strongly recom-
mends that the user read NFPA Standards 90A, 72, and 101.
The DH100 Air Duct Smoke Detectors are listed per UL 268A.

WARNING

This device will not operate without electrical power.

Fire situations may cause an interruption of power. The
system safeguards should be discussed with your local fire
protection specialist.

WARNING

This device will not sense smoke unless the ventilation sys-
tem is operating and the cover is installed.

WARNING

For this detector to function properly, it MUST be installed
according to the instructions in this manual. Furthermore,
the detector MUST be protected from the elements and op-
erated within ALL electrical and environmental specifica-
tions listed in this manual. Failure to comply with these
requirements may prevent the detector from activating
when smoke is present in the air duct.

Summary of Contents for Innovair DH100

Page 1: ...etc These actions can facilitate the management of toxic smoke and fire gases throughout the areas served by the duct system DH100 detectors are designed to operate with 12 or 24 VDC UL listed compatible 2 wire control panels Alarm current must be limited to 100mA or less by the control panel Auxiliary relay contacts for control purposes are not available for use with the DH100 Control must ini ti...

Page 2: ...pling tube end plug 11 One telescoping sampling tube 12 One 8 self tapping screw for the telescoping sampling tube NOTE For ducts over 11 2 feet longer inlet sampling tubes must be ordered to complete the installation They must be the correct length for the width of the duct where they will be installed See Table 1 on page 3 to determine the inlet tube required for different duct widths 5 Installa...

Page 3: ... Than 8 Feet Wide 1 If the tube is longer than the width of the air duct drill a 3 4 inch hole in the duct opposite the hole already cut for the inlet tube Make sure the hole is 1 to 2 below the in let hole on the opposite side of the duct to allow for mois ture drainage If the tube is shorter than the width of the air duct install the end plug into the inlet tube as shown in Figure 4 Sampling tub...

Page 4: ...nside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fasten the sampling tube to the other side of the duct When using the flange connector mounting technique drill a 1 to 11 4 inch hole where the flange will be used 5 4 3 Modifications of Inlet Sampling Tubes The...

Page 5: ...Smoke Detector Maintenance And Test Procedures Test and maintain duct smoke detectors as recommended in NFPA 72 The tests contained in this manual were devised to assist main tenance personnel in verification of proper detector operation Before conducting these tests notify the proper authorities that the smoke detection system will be temporarily out of service Disable the zone or system under te...

Page 6: ... INITIATION LOOP EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 1 2 3 4 5 6 7 3 4 5 Test Test Reset Reset Test Reset RA RA V Out V In 8 7 8 V In V Out V In V In V Out DH100 RTS451 KEY 6 2 1 Alarm LED No Connection Panel Figure 8 Wiring diagram for RTS451 RTS451KEY Remote Test S...

Page 7: ...ing Procedures Notify the proper authorities that the smoke detector sys tem is undergoing maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 7 1 Air Filters 1 Turn off power to the system 2 Remove and inspect sampling tube filters 3 If filters are heavily coate...

Page 8: ...he obligations or limitations of this Warranty The Company s obligation of this Warranty shall be limited to the repair or re placement of any part of the air duct smoke detector which is found to be defective in materials or workmanship under normal use and service dur ing the three year period commencing with the date of manufacture After phoning System Sensor s toll free number 800 SENSOR2 736 ...

Reviews: