background image

  

I56-3102-003 

 

 7/8/2019

D4120A Duct Smoke Detector

D4SA Sensor Component

D4P120A Power Board Component

INSTALLATION AND MAINTENANCE INSTRUCTIONS

3333 Unity Drive, Mississauga, ON L5L 3S6

1-800-SENSOR2, FAX: 905-812-0771

www.systemsensor.ca

TABLE OF CONTENTS 

PAGE

[1] Limitations of Duct Smoke Detectors 

1

[2] Exploded View of Duct Smoke Detector Components 2

[3] General Description 

2

[4] Contents of Duct Smoke Detector Kit 

2

[5] Detector Installation 

2

[6] Sampling Tube Installation 

3

[7] Measurement Tests 

3

[8] Field Wiring Installation Guidelines 

4

[9] Unit Configuration 

5

[10] Detector Status Indication 

6

[11] Interconnection (Multiple Fan Shut Down) 

6

[12] Verification of Operation 

6

[13] Detector Cleaning Procedures 

7

[14] Sensor replacement 

7

[15] Optional Accessories 

7

Wiring Diagrams 

5-7

Warranty 8

BEFORE INSTALLING

Read the System Sensor Guide for Proper Use of Smoke Detectors in Duct 

Applications (HVAG53), which provides information on detector spacing, 

placement, zoning, wiring, and special applications. This manual is available 

online at www.systemsensor.ca. CAN/ULC S524 should also be referenced 

for detailed information. 

NOTICE:

 This manual shall be left with the owner/user of this equipment.

NOTE:

 The D4120A duct detector consists of D4P120A Power Board component and the D4SA Sensor component.

SPECIFICATIONS 

Operating Temperature: 

D4120A & D4SA: –4° to 158° F (–20° to 70° C) D4P120A: –40° to 158° F (–40° to 70° C)

Storage Temperature: 

D4120A & D4SA: –22° to 158° F (–30° to 70° C) D4P120A: –40° to 158° F (–40° to 70° C)

Humidity: 

0% to 95% Relative Humidity Non-condensing

Air Velocity: 

100 to 4000 ft./min. (0.5 to 20.3 m/sec.)

D4120A Footprint Dimensions: 

Rectangular - 14.38 in L x 5 in W x 2.5 in D (37cm L x 12.7cm W x 6.36cm D)

 

Square - 7.75 in L x 9 in W x 2.5 in D (19.7cm L x 22.9cm W x 6.35cm D)

D4SA/D4P120A Footprint Dimensions: 7.75 in L x 5 in W x 2.5 in D (19.7cm L x 12.7cm W x 6.35cm D)

D4120A Weight: 

2.5 pounds; 1.14 kg

Electrical

Power supply voltage: 

20-29 VDC 

24 VAC 50-60-Hz 

120 VAC 50-60 Hz

Input capacitance: 

270 µF max. 

270 µF max. 

N/A

Reset Voltage: 

3.0 VDC min. 

2.0 VAC min. 

10 VAC min.

Reset Time (with RTS451): 

.03 to 0.3 sec. 

.03 to 0.3 sec. 

.03 to 0.3 sec.

Reset Time (by power down): 

0.6 sec. max. 

0.6 sec. max. 

0.6 sec. max.

Power Up Time: 

35 sec. max. 

35 sec. max. 

35 sec. max.

Alarm response time: 

15 sec. 

15 sec. 

15 sec.

Sensitivity Test: 

See detector label 

See detector label 

See detector label

Current Requirements (Using No Accessories)

Standby current 

21 mA @ 24 VDC 

65 mA RMS @ 24VAC 60Hz 

20 mA RMS @ 120 VAC 60 Hz

Alarm current 

65 mA @ 24 VDC 

135 mA RMS @ 24 VAC 60 Hz  35 mA RMS @ 120 VAC 60 Hz

CONTACT RATINGS

Alarm initiation contacts 

(SPST)

2.0A @ 30 VDC (resistive)

Alarm auxiliary contatcs 

(DPDT)

10A @30 VDC (resistive) 

10A @250 VAC (resistive)

1

/

2

 HP @240 VAC

1

/

4

 HP @120 VAC

NOTE: Alarm auxiliary contacts shall not be connected to initiating 

circuits of control panels. Use the alarm initiation contact for this 

purpose.
Supervisory Contacts 

(SPDT)

2.0A @ 30 VDC (resistive)

2.0A @ 125 VAC (resistive)

ACCESSORY CURRENT LOADS AT 24 VDC

DEVICE

STANDBY

TROUBLE

ALARM

MHRA/MHWA

0mA

n/a

29mA Max.

RA400ZA

0mA

n/a

12mA Max.

RTS451

0mA

n/a

12mA Max.

RTS451KEYA

12mA

n/a

12mA Max.

NOTE: Any combination of accessories may be used such that the given 

accessory loads are: 110mA or less at the Aux output, and 50mA or less at 

the Alarm output.

IMPORTANT:

 This detector must be tested and maintained regularly follow-

ing CAN/ULC S536 requirements. The detector should be cleaned at least 

once a year.

[1] LIMITATIONS OF DUCT SMOKE DETECTORS 

WARNING

The National Fire Protection Association has established that DUCT DETEC-

TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DE-

TECTOR PROTECTION as a means of providing life safety. Nor are they a 

substitute for early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user 

read NFPA Standards 90A, 72, 101and CAN/ULC S524. The D4120A Air 

Duct Smoke Detectors are listed per ULC.
This device will not operate without electrical power. Fire situations may 

cause an interruption of power. The system safeguards should be discussed 

with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating 

and the cover is installed.
For this detector to function properly, it MUST be installed according to the in-

structions in this manual. Furthermore, the detector MUST be operated within 

ALL electrical and environmental specifications listed in this manual. Failure 

to comply with these requirements may prevent the detector from activating 

when smoke is present in the air duct.

I56-3

10

2-00

3

Summary of Contents for Innovair flex D4120A

Page 1: ...Up Time 35 sec max 35 sec max 35 sec max Alarm response time 15 sec 15 sec 15 sec Sensitivity Test See detector label See detector label See detector label Current Requirements Using No Accessories St...

Page 2: ...el D4120A detectors are designed to be used in air handling systems with air velocities of 100 to 4000 feet per minute Duct widths from 6 inches to 12 feet can be accommodated Be sure to check enginee...

Page 3: ...duct the tube should extend out of the opposite side of the duct Drill a 3 4 inch hole in the duct opposite the hole already cut for the sampling tube Ensure that the sampling tube is angled downward...

Page 4: ...g plate screw See Figure 7 on page 5 for system wiring 8 2 SENSOR 2 INSTALLATION WIRING The power board is capable of controlling a second housed sensor The sec ond sensor model D4SA can be wired to t...

Page 5: ...NOTE 4 Initiation contacts shown in standby position Closed contacts indi cate an activated condition to the panel See specifications for contact ratings H0558 02CDN Designation Default Selection Fea...

Page 6: ...ating outside its original factory preset sensitivity and shall be cleaned or replaced See Section 9 for reference Also the GEMINI model 501 aerosol generator can be used for smoke entry testing Set t...

Page 7: ...f the fire department 13 1 DETECTOR SENSOR 1 Remove the sensor to be cleaned from the system 2 Remove the sensor cover by pulling outward on each of the four re moval tabs that hold the cover in place...

Page 8: ...the base in the sensor housing RED Blink every 5 seconds Alternating Green amber every 1 second Supervisory relay Terminals 3 and 14 are open Alarm Relay Terminals 4 and 5 are open Aux Relay does not...

Reviews: