background image

  

I56-3102-003 

 

 7/8/2019

[10] DETECTOR STATUS INDICATION

Detector Staus is indicated by the LED sensor, and the correcsponding LED 

on the power board. The power board has two separate LED’s to indicate the 

status of each sensor connected to it. Refer to Table 3 on page 8 for more 

details.

[11] INTERCONNECTION (MULTIPLE FAN SHUT DOWN)

When using the interconnect feature, an alarm from an initiating device will 

switch the Aux Relays on the other devices interconnected.

FIGURE 8. MULTIPLE FAN SHUTDOWN 

(INTERCONNECTION OF D4120A’S)

DETECTOR 1

120 VAC

D4120A

C, AUX A
NC, AUX A

50

DET.   

MAX.

INT/AUX–
INT+

SYSTEM CONTROL 

POWER, FAN 

CONTROL OR 

THERMOSTAT

SYSTEM CONTROL 

POWER, FAN 

CONTROL OR 

THERMOSTAT

12

1

+

2

11

15

20

19

9

10

16

6

5

13

3

14

17

8

18

7

4

DETECTOR 2

120 VAC

D4120A

C, AUX A
NC, AUX A

INT/AUX–
INT+

12

1

+

2

11

15

20

19

9

10

16

6

5

13

3

14

17

8

18

7

4

H0552-00CDN

FIGURE 9. MULTIPLE FAN SHUTDOWN 

(INTERCONNECTION OF D4120A TO DH100ACDC)

DH100ACDC

DH100ACDC

D4120A

D4120A

D4120A

  

 

 

 H0617-00CDN

[11.1] IMPORTANT INTERCONNECTION NOTES

•  When using the interconnect feature, all interconnected units must be 

powered using the same independent supply.

•   Polarity must be maintained throughout the interconnect wiring. 

Connect the INT+ terminal on unit 1 to the INT+ terminal on unit 2 and 

so on. Similarly, connect the INT/AUX- terminal on unit 1 to the INT/

AUX- terminal on unit 2 and so on.

•  Up to 50 D4120A units may be interconnected.
•  Up to 10 DH100ACDC units may be interconnected. Please note that 

each of the 9 DH100ACDC units interconnected can be substituted by 

three D4P120A units. Therefore, when using the interconnect feature 

a single DH100ACDC can drive either 9 DH100ACDC’s or 27 D4120A 

units. 

NOTE: Alarm can be reset only at the initiating device and not at the devices 

interconnected.

[12] VERIFICATION OF OPERATION

[12.1] FIELD SELECTABLE SETTINGS

Verify dip switch settings as per Table 2 on Page 5.

[12.2] POWERING THE UNIT

Apply 24 VDC power to 9 and 10 terminals on the D4P120A or apply 120 

VAC on terminals named 120VAC. See Figure 7 and electrical specifications 

for details.

[12.3] PERFORM DETECTOR CHECK

VERIFY STANDBY AND TROUBLE TEST per Table 3 on page 8. The use 

of a remote accessory for visible indication of power and alarm is recom-

mended.
NOTE: If an instantaneous tamper delay is selected a trouble may be indi-

cated with the cover installed.

[12.4] SENSITIVITY VERIFICATION

The sensitivity of the sensor is confirmed to be operating within its allowable 

range each time the sensor and power board LEDs blink green every 5 sec-

onds. Note in a maintenance condition the sensor LEDs will blink red every 

5 seconds and power board will blink amber as depicted in 

Table 3 

on page 

8. The maintenance condition indicates that the sensor is operating outside 

its original factory preset sensitivity and shall be cleaned or replaced. See 

Section 9 for reference. Also,the GEMINI model 501 aerosol generator can 

be used for smoke entry testing. Set the generator to represent 4%/ft to 5%/ft 

obscuration as described in the GEMINI 501 manual. Using the bowl shaped 

applicator, apply aerosol until the panel alarms.

[12.5] DETECTOR CLEANING PROCEDURES

Notify the proper authorities that the smoke detector system is undergoing 

maintenance, and that the system will temporarily be out of service. Disable 

the zone or system undergoing maintenance to prevent unwanted signalling 

and possible dispatch of the fire department.

[12.5.1] ALARM TESTS

1a.   Test/Reset Button - Press and hold the test button located on the power 

board cover for at least 2 seconds.

     OR
1b.   M02-04-00 Magnet Test - Place the painted surface of the magnet onto 

the MAGNET TEST location on the sensor cover of unit (Figure 1).

     OR
1c.   Remote Test Accessory - See list on page 1.
 

 The red alarm LED on the sensor and the power board should latch 

on, as should any accessories (i.e. RA400ZA, RTS451). Verify system 

control panel alarm status and control panel execution of all intended 

auxiliary functions (i.e fan shutdown, damper control, etc.). 

2.   The detector must be reset by the system control panel, front cover Test/

Reset button, or remote accessory.

3.   To reset using the Test/Reset button on the power board cover simply 

Press and release.

4.   Verify airflow test per Section 7 has been performed.

[12.5.2] SMOKE RESPONSE TESTS

To determine if smoke is capable of entering the sensing chamber, visually 

identify any obstructions. Plug the exhaust and sampling tube holes to pre-

vent ducted air from carrying smoke away from the detector head, then blow 

smoke such as cigarette, cotton wick, or punk directly at the head to cause an 

alarm. REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST, OR THE 

DETECTOR WILL NOT FUNCTION PROPERLY.

[12.5.3] SMOKE ENTRY USING AEROSOL SMOKE

This test is intended for low-flow systems (100-500 FPM). If the air speed is 

greater than 500 FPM, use a conventional manometer to measure differential 

pressure between the sampling tubes, as described in Section 7.1.
Drill a 

1

4

 inch hole 3 feet upstream from the duct smoke detector. With the air 

handler on, measure the air velocity with an anemometer. Air speed must be 

at least 100 FPM. Spray aerosol smoke* into the duct through the 

1

4

 inch hole 

for five seconds. Wait two minutes for the duct smoke detector to alarm. If the 

duct smoke detector alarms, air is flowing through the detector. Remove the 

duct smoke detector cover and blow out the residual aerosol smoke from the 

chamber and reset the duct smoke detector. Use duct tape to seal the aerosol 

smoke entry hole.
*Aerosol smoke can be purchased from Home Safeguard Industries, model 

25S Smoke Detector Tester, Malibu, CA. Phone: 310/457-5813. When used 

properly, the canned smoke agent will cause the smoke detector to go into 

Summary of Contents for Innovair flex D4120A

Page 1: ...Up Time 35 sec max 35 sec max 35 sec max Alarm response time 15 sec 15 sec 15 sec Sensitivity Test See detector label See detector label See detector label Current Requirements Using No Accessories St...

Page 2: ...el D4120A detectors are designed to be used in air handling systems with air velocities of 100 to 4000 feet per minute Duct widths from 6 inches to 12 feet can be accommodated Be sure to check enginee...

Page 3: ...duct the tube should extend out of the opposite side of the duct Drill a 3 4 inch hole in the duct opposite the hole already cut for the sampling tube Ensure that the sampling tube is angled downward...

Page 4: ...g plate screw See Figure 7 on page 5 for system wiring 8 2 SENSOR 2 INSTALLATION WIRING The power board is capable of controlling a second housed sensor The sec ond sensor model D4SA can be wired to t...

Page 5: ...NOTE 4 Initiation contacts shown in standby position Closed contacts indi cate an activated condition to the panel See specifications for contact ratings H0558 02CDN Designation Default Selection Fea...

Page 6: ...ating outside its original factory preset sensitivity and shall be cleaned or replaced See Section 9 for reference Also the GEMINI model 501 aerosol generator can be used for smoke entry testing Set t...

Page 7: ...f the fire department 13 1 DETECTOR SENSOR 1 Remove the sensor to be cleaned from the system 2 Remove the sensor cover by pulling outward on each of the four re moval tabs that hold the cover in place...

Page 8: ...the base in the sensor housing RED Blink every 5 seconds Alternating Green amber every 1 second Supervisory relay Terminals 3 and 14 are open Alarm Relay Terminals 4 and 5 are open Aux Relay does not...

Reviews: