background image

  

I56-3102-003 

 

 

©2019 System Sensor. 7/8/2019

THREE-YEAR LIMITED WARRANTY

System Sensor warrants its enclosed product to be free from defects in materials and 

workmanship under normal use and service for a period of three years from date of man-

ufacture. System Sensor makes no other express warranty for the enclosed product. No 

agent, representative, dealer, or employee of the Company has the authority to increase 

or alter the obligations or limitations of this Warranty. The Company’s obligation of this 

Warranty shall be limited to the replacement of any part of the product which is found to 

be defective in materials or workmanship under normal use and service during the three 

year period commencing with the date of manufacture. After phoning System Sensor’s 

toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send de-

fective units postage prepaid to: System Sensor Canada (3PL), c/o Kuehne and Nagel, 

6335 Edwards Blvd., Mississauga, Ontario L5N 2W7, RA #__________. Please include 

a note describing the malfunction and suspected cause of failure. The Company shall 

not be obligated to replace units which are found to be defective because of damage, 

unreasonable use, modifications, or alterations occurring after the date of manufacture. 

In no case shall the Company be liable for any consequential or incidental damages for 

breach of this or any other Warranty, expressed or implied whatsoever, even if the loss 

or damage is caused by the Company’s negligence or fault. Some states do not allow 

the exclusion or limitation of incidental or consequential damages, so the above limita-

tion or exclusion may not apply to you. This Warranty gives you specific legal rights, and 

you may also have other rights which vary from state to state.

Please refer to insert for the Limitations of Fire Alarm Systems

TABLE 3. DETECTOR STATUS INDICATION

NOTE: There are two LED’s on the Power board D4P120A, each indicating the Status of the two sensors connected. When 

there is only one sensor connected, LED2 will remain off.

Sensor

D4S

Power Board 

D4P120

At power-up or reset at the panel, the
sensor will take approx 45 seconds 
to initialize. Also occurs if the sensor 
has been removed and restored in 
the base in the sensor housing.

RED Blink every 5 
seconds

Alternating
Green/amber
every 1 second

Supervisory relay

: Terminals 3 and 14 are open.                                                                                               

Alarm Relay

: Terminals 4 and 5 are open.                                                                                                  

Aux Relay

 does not switch states:Terminals 6 and 16 are closed,Terminals 8 and 18 are closed

Sensor is missing during the seven 
minute tamper Delay, if selected.

Off

Alternating
Green/amber
every 1 second

Supervisory relay

: Terminals 3 and 14 are closed                                                                                              

Alarm Relay

: Terminals 4 and 5 are open.                                                                                                  

Aux Relay

 does not switch states:Terminals 6 and 16 are closed,Terminals 8 and 18 are closed

Maintenance

Sensor D4S is outside it's UL 
approved sensitivity limits and needs 
to be cleaned or replaced.

RED Blink every 5 
seconds

Amber Blink 
every 5 seconds

Supervisory relay

: Terminals 3 and 14 are 

closed

.                                                                                               

Alarm Relay

: Terminals 4 and 5 are open.                                                                                                  

Aux Relay

 does not switch states:Terminals 6 and 16 are closed,Terminals 8 and 18 are closed

.Unit loses Power                                 Off

Off

.Cover Tamper Delay times out

Green Blink every 5 
seconds

Amber solid

.Wiring Problems between the 
Sensor and the Power Board

Off

Amber solid

.Mismatch between the number of 
sensors connected and the Dip 
Switch setting

1 sensor connected,2 selected

Green blink every 5 
seconds on first 
sensor.                      
No second sensor.

LED1 Green 
blink every 5 
seconds
LED2 Amber 
solid

2 sensors connected,1 selected

Green blink every 5 
seconds on first 
sensor.                    
LED's off on second 
sensor

LED1 Green 
blink every 5 
seconds
LED2 Amber 
solid

Alarm

Unit detects smoke

Solid Red

Solid Red

Supervisory relay

: Terminals 3 and 14 are closed                                                                                              

Alarm Relay

: Terminals 4 and 5 are closed.                                                                                                

Aux Relay

 switches states: Terminals 6 and 16 are open, Terminals 8 and 18 are open 

Standby

Unit has Power and it is not in 
initialization, Trouble, Maintenance or
Alarm.

Green Blink every 5 
seconds

Green Blink 
every 5 seconds

Supervisory relay

: Terminals 3 and 14 are closed                                                                                              

Alarm Relay

: Terminals 4 and 5 are open.                                                                                                  

Aux Relay

 does not switch states: Terminals 6 and 16 are closed, Terminals 8 and 18 are closed

LED Status

Status

Description

Status of Relays

Supervisory relay

: Terminals 3 and 14 are open.                                                                                               

Alarm Relay:

 Terminals 4 and 5 are open.                                                                                                   

Aux Relay

 does not switch states with no shutdown on Trouble selected:                                                         

Terminals 6 and 16 are closed. Terminals 8 and 18 are closed.                                                                  

Aux Relay

 Switches states with shutdown on Trouble selected:                                                                         

Terminals 6 and 16 are open, Terminals 8 and 18 are open   

Trouble 

 Sensor 

Initialization

Summary of Contents for Innovair flex D4120A

Page 1: ...Up Time 35 sec max 35 sec max 35 sec max Alarm response time 15 sec 15 sec 15 sec Sensitivity Test See detector label See detector label See detector label Current Requirements Using No Accessories St...

Page 2: ...el D4120A detectors are designed to be used in air handling systems with air velocities of 100 to 4000 feet per minute Duct widths from 6 inches to 12 feet can be accommodated Be sure to check enginee...

Page 3: ...duct the tube should extend out of the opposite side of the duct Drill a 3 4 inch hole in the duct opposite the hole already cut for the sampling tube Ensure that the sampling tube is angled downward...

Page 4: ...g plate screw See Figure 7 on page 5 for system wiring 8 2 SENSOR 2 INSTALLATION WIRING The power board is capable of controlling a second housed sensor The sec ond sensor model D4SA can be wired to t...

Page 5: ...NOTE 4 Initiation contacts shown in standby position Closed contacts indi cate an activated condition to the panel See specifications for contact ratings H0558 02CDN Designation Default Selection Fea...

Page 6: ...ating outside its original factory preset sensitivity and shall be cleaned or replaced See Section 9 for reference Also the GEMINI model 501 aerosol generator can be used for smoke entry testing Set t...

Page 7: ...f the fire department 13 1 DETECTOR SENSOR 1 Remove the sensor to be cleaned from the system 2 Remove the sensor cover by pulling outward on each of the four re moval tabs that hold the cover in place...

Page 8: ...the base in the sensor housing RED Blink every 5 seconds Alternating Green amber every 1 second Supervisory relay Terminals 3 and 14 are open Alarm Relay Terminals 4 and 5 are open Aux Relay does not...