background image

SS-300-018 

I56-3371-003R

DNRW Duct Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

Table of Contents 

Page

[1] Limitations of Duct Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . .1
[2] General Description  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
[3] Contents of the Duct Smoke Detector Kit . . . . . . . . . . . . . . . . . . . . . .1
[4] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
[5] Sampling Tube Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
[6] Measurement Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
[7] Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
[8] Verification of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
[9] Dectector Cleaning Procedures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
[10] Sensor Replacement  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
[11] Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Warranty 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

BEfORE INSTALLINg

Read the System Sensor Guide for 

Proper Use of Smoke Detectors in Duct Appli-

cations

 (A05-1004), which provides detailed information on detector spacing, 

placement,  zoning,  wiring,  and  special  applications.  Copies  of  this  manual 
are available online at www.systemsensor.com. NFPA Standards 72 and 90A 
should also be referenced for detailed information. 

NOTICE: This manual shall be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly following 
NFPA 72 requirements. The detector should be cleaned at least once a year.

[1]LIMITATIONS Of DUCT SMOkE DETECTORS 

WARNING

The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR 
PROTECTION as a means of providing life safety. Nor are they a substitute for 
early warning in a building’s regular fire detection system.

System Sensor supports this position and strongly recommends that the user 
read NFPA Standards 90A, 72, and 101. The DNRW Air Duct Smoke Detectors 
are listed per UL 268A.

This device will not operate without electrical power. Fire situations may cause 
an  interruption  of  power.  The  system  safeguards  should  be  discussed  with 
your local fire protection specialist.

This  device  will  not  sense  smoke  unless  the  ventilation  system  is  operating 
and the cover is installed.

For  this  detector  to  function  properly,  it  MUST  be  installed  according  to  the 
instructions in this manual. Furthermore, the detector MUST be operated within 
ALL electrical and environmental specifications listed in this manual and the 
sensor head installation manual. Failure to comply with these requirements may 
prevent the detector from activating when smoke is present in the air duct.

[2]gENERAL DESCRIPTION

Smoke introduced into this air duct system will be distributed throughout the 
entire building. Smoke detectors designed for use in air duct systems are used 
to sense the presence of smoke in the duct. 

Model  DNRW  Air  Duct  Smoke  Detector  utilizes  photoelectric  technology 
for the detection of smoke. This detection method, when combined with an  
efficient  housing  design,  samples  air  passing  through  the  duct  and  allows  
detection  of  a  developing  hazardous  condition.  When  sufficient  smoke  is 
sensed,  an  alarm  signal  is  initiated  at  the  fire  control  panel  monitoring  the 
detector, and appropriate action can be taken to shut off fans, blowers, change 
over air handling systems, etc. These actions can facilitate the management of 
toxic smoke and fire gases throughout the areas served by the duct system.

The DNRW incorporates a sensor cover tamper feature that provides a trouble 
signal at the panel immediately if the cover is removed or improperly installed.  
Proper installation of the sensor cover removes the trouble condition.

If programmed with the system control panel, two LEDs on each duct smoke 
detector light to provide local visible indication.  

The  DNRW  provides  a  remote  alarm  output  for  use  with  auxiliary  devices, 
such as the RA400Z/RA100Z remote LED annunciator, as well as remote test 
capability  with  the  RTS451/RTS151  or  RTS451KEY/RTS151KEY  Remote  Test 
Stations.

[2.1] DETECTOR fEATURE SET

- Utilizes plug-in head

- Sampling tubes install from front and rear

- Compatible with existing accessories

- Able to address detector per code switches on sensor head.

[3]CONTENTS Of ThE DUCT SMOkE DETECTOR kIT

1.   Sensor/power  board  assembly  and  covers  (use  appropriate  sensor  per 

the system control panel)

2.  Three #10 sheet metal screws for mounting
3.  One test magnet
4.  Drilling template
5.  One sampling tube end cap
6.  One plastic exhaust tube
NOTE: A sampling tube must be ordered to complete the installation. It must 
be  the  correct  length  for  the  width  of  the  duct  where  it  will  be  installed. 
See Table 1 on page 3 to determine the inlet tube required for different duct 
widths. 

[4]DETECTOR INSTALLATION 
[4.1]VERIfy DUCT AIR fLOW DIRECTION AND VELOCITy

Model  DNRW  detectors  are  designed  to  be  used  in  air  handling  systems  
having air velocities of 100 to 4000 feet per minute. Duct widths from 6 inches 
to 12 feet can be accommodated. Be sure to check engineering specifications to 
ensure that the air velocity in the duct falls within these parameters. If neces-
sary, use a velocity meter (anemometer) to check the air velocity in the duct.

I56-337

1-00

3R

SPECIfICATIONS 

Operating Temperature: 

–4° to 158° F (–20° to 70° C); 

 

32° F to 120° F (0° C to 49° C) with module installed in the DNRW

Storage Temperature: 

–22° to 158° F (–30° to 70° C)

Environmental Rating: 

NEMA 4* Type 4 Enclosure — Watertight

Humidity: 

0% to 93% Relative Humidity Non-condensing

Air Velocity: 

100 to 4000 ft./min. (0.5 to 20.3 m/sec.)

Rectangular Footprint Dimensions: 

14.38 in L x 5 in W x 2.5 in D (37 cm L x 12.7 cm W x 6.36 cm D)

Square Footprint Dimensions: 

7.75 in L x 9 in W x 2.5 in D (19.7 cm L x 22.9 cm W x 6.35 cm D)

Weight: 

1.6 pounds; 0.73 kg

Electrical (See applicable detector head installation manual for electrical specifications. Use the Base/Sensor Cross Reference chart at http:\\www.systemsensor.com 
to determine applicable sensor head.)

ACCESSORY CURRENT LOADS AT 24 VDC

DEVICE

STANDBY

ALARM

RA400Z/RA100Z

0mA

12mA Max.

RTS451/RTS151

0mA

12mA Max.

RTS451KEY/
RTS151KEY

12mA

12mA Max.