background image

RA100Z and RA100ZA (Canadian) 

Remote Annunciator

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

NOTE: RA100Z and RA100ZA replaces RA400Z and RA400ZA .

GENERAL INFORMATION

The National Fire Protection Association has published codes, standards, and 
recommended practices for the installation and use of the above appliance. It 
is recommended that the installer be familiar with these requirements, with 
local codes, and any special requirements of the local authority having juris-
diction.

The models RA100Z & RA100ZA remote annunciators are polarized devices 
designed for both conventional and intelligent applications. They have been 
designed using an active current regulator so that the maximum current re-
quired from the system is 10mA when the input voltage is within the specified 
voltage range.

INSTALLATION

The remote annunciator is intended to be mounted to a single gang electrical 
outlet box. The wiring must be in compliance with all codes. The device must 
be operated within its published specifications.

Wire the remote annunciator according to the instructions supplied with the 
device being monitored. Polarity of the incoming wires must be observed and 
connected to the proper terminals “+” and “–”. (See Figure 2.) 

The provided jumper must be installed for use with System Sensor Conventional 
systems. To install jumper: slide jumper over both pins. (see Figure 3/Note 1)

H0355-01

SPECIFICATIONS

Voltage Range 
Conventional System: 

3.1 to 32 VDC  — (Installation of jumper required) Note 1

Intelligent System: 

18 to 32 VDC — (Do not install jumper)

Maximum Alarm Current: 

10 mA maximum.

Temperature Range: 

–10° to 60°C (14° to 140°F)

Listing: 

UL, FM, CE

CAUTION

Install jumper when using an RA100Z or RA100ZA with any conventional duct detector (such as the System Sensor model D2 or D4120).

I56-0

508-008

FIGURE 1:

  

I56-0508-008 

 

 06-10

Reviews: