For signal wiring (the wiring between interconnected sensors 
or modules), it is recommended that the wire be no smaller 
than 18 gauge (1.0 square mm). Wire sizes up to 12 gauge (2.5 
square mm) may be used with the base. For best system per-
formance, the power (+ and –) wires and the communication 
circuit wires should be twisted pair or shielded cable installed 
in  separate  grounded  conduit  to  protect  the  communication 
loop from electrical interference.
Make wire connections by stripping about 

3

8

” of insulation 

from  the  end  of  the  wire.  Then,  slide  the  bare  end  of  the 
wire  under  the  clamping  plate,  and  tighten  the  clamping 
plate screw. Do NOT loop the wire under the clamping plate 
(See 

Figure 3

).

The zone wiring of the sensor base should be checked before 
the sensor heads are installed. Check the wiring for continuity 
and polarity in the base.
See the individual sensor manual for the maximum sensor in-
stallation temperature.

Wiring Instructions

NOTE:  External  supply  shown  in  normal  standby  configura-
tion in 

Figure 4

 and 

5

.

The wiring diagram for a typical 2-wire intelligent system is 
shown in 

Figure 4

 and 

5

 (the monitor module is supervising 

the external supply).

Testing

Sensors and bases must be tested after installation and as an inte-
gral part of periodic maintenance. Test the B501BHT as follows:

NOTE:

  Before  testing,  notify  the  proper  authorities  that  the 

smoke sensor system is undergoing maintenance and, there-
fore, will be temporarily out of service. Disable the system un-
dergoing maintenance to prevent unwanted alarms.
1.   If configured as in 

Figure 4

 or 

5

, reverse the polarity of the 

external 24VDC supply. If configured as in 

Figure 5

, turn 

on the Intelligent Relay Module. All B501BHT bases on the 
loop should sound in approximately 10 seconds.

2.   Latch the sensor LED on from the control panel. That unit’s 

B501BHT should sound in approximately 10 seconds.

NOTES: 

1.   There  is  approximately  a  10  second  delay  built  into  the 

B501BHT before sounding. This delay is present whether 
the control signal comes from the sensor or from the exter-
nal power supply polarity being reversed.

2.   During  automatic  testing  cycles,  the  horn  may  sound  if 

the associated sensor is left in the test mode with LEDs 
latched on for more than 4 seconds. Therefore, it is neces-
sary to complete testing of each sensor within this 4-sec-
ond limit to prevent the horn from sounding.