FDR-3G
Type of activation GST0
IMPORTANT: Risk of electric shock!
Switch off the power supply before working on any electrical equipment.
Only qualified electricians are allowed to work on the electrical system.
This type of activation is with a Gruner supply and communication unit fs-UFC24-2 (other communication units on
demand).
Actuator power supply: AC (50/60 Hz)/DC 24 V
NOTES:
• The actuator and the control module are factory wired.
• Individual control of 2 fire dampers
• Bus protocols (RS-485): BACnet MS/TP and Modbus RTU
• Automatic baud rate detection with BACnet
• Bus monitoring function
LEDs status indication (GST0)
LED color and type | LED state | Status
Yellow (Closed) | ON | Damper closed
Green (Open) | ON | Damper open
Yellow and green | Blinks in parallel | Damper is moving
Yellow and green | Alternately blinks - interval 0.5 sec | Actuator did not reach the end switch position within set time
Yellow and green | Alternately blinks - interval 3 sec | Alarm active at damper: bus command = actuator open, actuator
= in closed position
Power green | OFF | Power failure
Power green | ON | Power is connected
Yellow Rx | Blinks | Receive data
Green Tx | Blinks | Transmit data
Summary of Contents for 163262
Page 1: ...FDR 3G Circular Fire Damper Handbook ...
Page 19: ...19 67 FDR 3G ...
Page 20: ...20 67 FDR 3G ...
Page 23: ...23 67 FDR 3G ...
Page 24: ...24 67 FDR 3G ...
Page 27: ...27 67 FDR 3G ...
Page 28: ...28 67 FDR 3G ...
Page 31: ...31 67 FDR 3G ...
Page 33: ...33 67 FDR 3G Notes ve Vertical wall 1 Smaller distances maximum resistivity EI90 ve i o S ...
Page 35: ...35 67 FDR 3G ...
Page 36: ...36 67 FDR 3G ...
Page 39: ...39 67 FDR 3G ...
Page 40: ...40 67 FDR 3G ...
Page 67: ...Systemair DESIGN 2022 07 11 Handbook_FDR_3G_en GB Original instructions ...