FDR-3G
T
- Test button: This allows the simple function test on site of the damper. The button operation causes an error
message at the control device which must be reset.
X2
- 2-pin spring terminal: 1/2 - connection for SLC two-wire line, wires interchangeable. Maximum cable lengths can
be calculated with the SLC Planning Tool. Rule of thumb: 300m@1.5 mm2
X3
- 3-pin connector: damper actuator (DC 24 V)
X4
- 4-pin spring terminal: Connection for smoke detector
• 1- (+) DC 24 V / max. 30 mA
• 2- GND
• 3- IN1 (external relay contact 1)
• 4- IN2 (external relay contact 2)
X6
- 6-pin connector: damper actuator (position limit switches)