62/67 |
FDR-3G
Type of activation BST3
IMPORTANT: Danger of electric shock!
Switch off the power supply before working on any electrical equipment.
Allow only qualified electricians to work on the electrical system.
Actuator power supply via fitted communication unit: DC 24 V
NOTES:
• Depiction of parts for fitted communication and supply unit BKN230-24-C-MP (SBS/MP).
• The unit can communicate either with the BKS24...-1B, ...-9A control modules via an analogue 2-wire system or
digitally via a 2-wire connection to a BELIMO MP-Bus system.
LEDs status indication of actuator
LED colour| LED state | Status
Green | ON | Damper open
Green | Blinks | Damper is opening
Yellow | ON | Damper closed
Yellow | Blinks | Damper is closing
Red | ON | Internal device fault (BKN230-24-C-MP)
Red | Blinks | External fault: thermoelectrical device (BAT…) triggered; smoke detector triggered
Red | Blinks briefly | MP-Bus communication active (i.e. MP commands are being received)
LED signalization of communication unit (BKN230-24-C-MP)
LED colour| LED state
Command OPEN / limit position not reached:
Red | Blinks
Green | OFF
Yellow | Blinks
Yellow | Signaling after 150 seconds
Command CLOSE / limit position not reached:
Red | Blinks
Green | Blinks
Yellow | OFF
Yellow | Signaling after 150 seconds
Summary of Contents for 163262
Page 1: ...FDR 3G Circular Fire Damper Handbook ...
Page 19: ...19 67 FDR 3G ...
Page 20: ...20 67 FDR 3G ...
Page 23: ...23 67 FDR 3G ...
Page 24: ...24 67 FDR 3G ...
Page 27: ...27 67 FDR 3G ...
Page 28: ...28 67 FDR 3G ...
Page 31: ...31 67 FDR 3G ...
Page 33: ...33 67 FDR 3G Notes ve Vertical wall 1 Smaller distances maximum resistivity EI90 ve i o S ...
Page 35: ...35 67 FDR 3G ...
Page 36: ...36 67 FDR 3G ...
Page 39: ...39 67 FDR 3G ...
Page 40: ...40 67 FDR 3G ...
Page 67: ...Systemair DESIGN 2022 07 11 Handbook_FDR_3G_en GB Original instructions ...