64/67 |
FDR-3G
Type of activation BST10
IMPORTANT: Danger of electric shock! The BKN230-24-PL may only be used with a designated master (e.g. BKS64-PL).
Switch off the power supply before working on any electrical equipment.
Allow only qualified electricians to work on the electrical system.
Actuator power supply via fitted communication unit: DC 24 V
NOTES:
• Left: Connection scheme for fitted communication and supply unit BKN230-24-PL (Powerline)
• Right: Example connection scheme for smoke detector ORS 142 K from Hekatron - not part of the delivery.
230V
AC
L L N N
GND
+24V
IN
X8
GND
+24V
IN
ORS 142 K (Hekatron)
BKN230-24-PL
1
2
3
4
5
6
X200
U
X8
T
X300
X3
X6
Legend
U
- USB mini socket: reading of the MAC address, optionally setting the BUS-ID (1..64) and a device identifier in plain
text
T
- Test button: Test run / fault erase. Press the button for longer than one second to trigger the start of test run or
short press to erase stored error
X6 and X300 connector terminals are arranged so that only either a conventional actuator or a Belimo Top-Line
actuator can be connected.
X200
- 2+2-pin spring terminal: (50/60Hz) AC 230 V with Powerline signal.
X3
- 3-pin connector: damper actuator (DC 24 V).
X4
- 4-pin spring terminal: connection for smoke detector.
X6
- 6-pin connector: damper actuator (position limit switches).
X8
- 3-pin spring terminal: connection for smoke detector (without smoke detector: c24 V and IN).
• 1- GND.
• 2- (+) DC 24 V.
• 3- IN.
X300
- 4-pin connector: connection for belimo top-line actuator (not used).
Summary of Contents for 163262
Page 1: ...FDR 3G Circular Fire Damper Handbook ...
Page 19: ...19 67 FDR 3G ...
Page 20: ...20 67 FDR 3G ...
Page 23: ...23 67 FDR 3G ...
Page 24: ...24 67 FDR 3G ...
Page 27: ...27 67 FDR 3G ...
Page 28: ...28 67 FDR 3G ...
Page 31: ...31 67 FDR 3G ...
Page 33: ...33 67 FDR 3G Notes ve Vertical wall 1 Smaller distances maximum resistivity EI90 ve i o S ...
Page 35: ...35 67 FDR 3G ...
Page 36: ...36 67 FDR 3G ...
Page 39: ...39 67 FDR 3G ...
Page 40: ...40 67 FDR 3G ...
Page 67: ...Systemair DESIGN 2022 07 11 Handbook_FDR_3G_en GB Original instructions ...