FDR-3G
Assessed Performance - FDR-3G
19
CE
1396
Systemair Production a.s.
Hlavná 371, 900 43 Kalinkovo, Slovakia
1396-CPR-0162, FDR-3G
(valid for subgroups: …EX, …KS, …OF)
EN 15650 : 2010
Circular fire dampers
Nominal activation conditions/sensitivity -
Pass
• sensing element load bearing capacity
• sensing element response temperature
Response delay (response time) -
Pass
• closure time
Operational reliability -
Pass
• motorized cycle = 10.200 cycles
• manual cycle = 50 cycles
• modulated = 20.200 cycles
Fire resistance:
Resistivity depending on installation method and situation
• integrity
E
• maintenance of the cross section (under E)
• mechanical stability (under E)
• cross section (under E)
• insulation
I
• smoke leakage
S
Durability of response delay -
Pass
• sensing element response temperature and load bearing capacity
Durability of operational reliability -
Pass
• open and closing cycle