3/64 |
F-B90
Description
Fire dampers represent passive fire protection and are designed to utilize compartmentalization to prevent the spread
of toxic gases, smoke and fire. The opening and closure of the damper blade can be activated remotely for actuator
versions. In case of fire when the air in the duct exceeds 72 °C or 74 °C, the thermal fuse melts in both actuator and
manual versions. The melting of the thermal fuse activates the closure of the damper blade automatically. The damper
blade is then mechanically locked in the closed position.
Highlights
• Short body without blade overhangs
• Can be used as Air-transfer grille with cold smoke tightness
• Duct connection from both sides always available
• Symmetric structure and mechanism accessible from both sides
• Fit installation, filling not visible
• Available with smoke detection
• One sided duct connection ended with Grille
Fire Resistivity
F-B90 fire dampers are CE certified following the Construction Products Regulation according to EN 15650:2010.
Dampers are tested according to EN 1366-2:2015 and classified according to EN 13501-3 + A1:2009. The fire damper
together with its installation form an inseparable part of the fire resistivity rating. F-B90 fire dampers are designed for
the installations listed and described in their Handbook.
• Damper connected to duct on both sides or on one side only, installed within standard supporting construction in
accordance with EN 1366-2:2015:
EI90 (v
e
- h
o
i↔o)S
• Damper with grille on both sides and no duct connection (air transfer damper), installed within standard supporting
construction in accordance with EN 1366-2:2015:
EI90 (v
e
- i↔o)S
&
EI120 (v
e
- i↔o)
Types of Product
There are different types of F-B90 connection. Thus, there are several types of grilles:
•
00
– without grille.
Summary of Contents for 178818
Page 1: ...F B90 Multiblade Fire Damper Handbook...
Page 21: ...21 64 F B90 5 1 1 2 B A1 A2 3 A1 B A2...
Page 22: ...22 64 F B90 C1 C2 C3 C4 C5 i D 4 1 8 1 Fx D1 D2...
Page 23: ...23 64 F B90 F3 5 2 E F F3 E1 E2 5 F1 F2 6...
Page 48: ...48 64 F B90 Wire preparation C1 A1 A2 B C2 C2 H B G A1 A2 B 2 1 C2 C1...
Page 61: ...61 64 F B90 D1 D2 D3 P13 P13 E E H B G 1 2 H...
Page 64: ...Systemair DESIGN 2021 08 25 Handbook_F_B90_en GB...