Page 34
Technical data
AQVL HT
85
95
105
115
125
140
Power supply
V/ph/Hz
400V/3/50Hz
Number of refrigerant circuits
2
2
2
2
2
2
Total capacity steps
%
0-25-50-75-
100
0-25-50-75-
100
0-24-47-74-
100
0-25-50-75-
100
0-22-43-72-
100
0-25-50-75-
100
Refrigerant
Type / GWP
R410A / 2.088
Charge 1/2
(1)
kg
6 / 6
6 / 6
6 / 6
6 / 6
8 / 8
8 / 8
tCO
2
eq
12,5 / 12,5 12,5 / 12,5 12,5 / 12,5 12,5 / 12,5 16,7 / 16,7 16,7 / 16,7
Compressor
Type
Scroll
Number
4
4
4
4
4
4
Start-up type
Direct
Oil type
POE
N°of loading stages
0/100
0/100
0/100
0/100
0/100
0/100
Evaporator
Type
Plate
Number
1
1
1
1
1
1
Water flow rate
l/s
4,12
4,63
5,11
5,51
5,95
6,67
Pressure drop
kPa
Refers to Hydraulic features
Desuperheater
Type
Plate
Number
2
2
2
2
2
2
Water flow rate
l/s
1,05
1,18
1,30
1,40
1,53
1,72
Pressure drop
kPa
Refers to Hydraulic features
Fans
Type
Axial
Number
2
2
2
2
2
2
Nominal speed
rpm
1130
1130
1130
1130
1130
1130
Air flow rate
m³/s
13,81
13,81
13,6
13,4
14,5
14.1
Power input
kW
4,6
4,6
4,6
4,6
4,6
4,6
Air cooled condenser
Type
Coil
Number
2
2
2
2
2
2
Total coil face area per coil
m²
2,4
2,4
2,4
2,4
3,12
3,12
Hydraulic connections (Evapora-
tor)
Type
Male Gas Threaded
Inlet diameter
inch
2”1/2
2”1/2
2”1/2
2”1/2
2”1/2
2”1/2
Outlet diameter
inch
2”1/2
2”1/2
2”1/2
2”1/2
2”1/2
2”1/2
Hydraulic connections (Desu-
perheater)
Type
Male Gas Threaded
Inlet diameter
inch
1”
1”
1”
1”
1”
1”
Outlet diameter
inch
1”
1”
1”
1”
1”
1”
Weight
Shipping weight
kg
1033
1047
1084
1116
1151
1230
Operating weight
kg
1058
1072
1111
1143
1183
1262
Dimensions
Length
mm
2555
2555
2555
2555
3155
3155
Width
mm
1095
(1250)
1095
(1250)
1095
(1250)
1095
(1250)
1095
(1250)
1095
(1250)
Height
mm
2185
2185
2185
2185
2185
2185
(1)
The refrigerant value are indicative values for standard units. The actual data are indicated on the unit label.