36
8 - Technical Data (continued)
(1)
Sound levels are at fully loaded conditions. Sound power level values refer to ISO standard 3744 and Eurovent 8/1.
(2)
Sound pressure levels refer to ISO standard 3744, parallelepiped shape.
(*)
High efficiency units (HSE) with inverter fans.
Note:
Refrigerant charge data are indicative only. Always refer to data shown on the unit nameplate.
AQWL STD/HSE - ELN models
1404
1604
1806
2106
2406
Power supply
V/Ph/Hz
400 (±10%)/3/50
Number of refrigerant circuits
2
2
2
2
2
Refrigerant charge
kg
40 + 40
44 + 44
52 + 52
67 + 52
67 + 67
Total capacity steps
%
21-50-71-100
25-50-75-100
17-33-50-67-83-100 15-29-43-62-81-100 17-33-50-67-83-100
COMPRESSORS
Number
4
4
6
6
6
Type
Scroll
Oil type
POE
N° of loading stages
0/100
0/100
0/100
0/100
0/100
EVAPORATOR
Number
1
1
1
1
1
Type
PLATE
PLATE
PLATE
PLATE
PLATE
Water volume
l
33
35
38
38
40
AIR COOLED CONDENSER
Number of coils
4
4
4
4
4
Total coil face area per coil
m²
4.4
4.4
5.6
6.7
6.7
FANS
Number of fans
8
8
10
10
12
Nominal speed
rpm
550
550
550
550
550
Total airflow
m³/h
97000
91000
112000
122000
135000
Total input power
kW
9.6
9.6
12.0
12.0
14.4
Total input power
(*)
kW
2.6
2.6
3.2
3.2
3.8
External static pressure
Pa
0 Pa
WEIGHT
Shipping weight
kg
2633
2850
3559
3814
3932
Operating weight
kg
2668
2887
3599
3854
3975
ADDITIONAL WEIGHT
HSE version
kg
0
0
0
0
0
Desuperheater version
kg
Please consult factory
With pump/s
kg
With pump/s and tank
kg
Copper Fins
kg
SOUND LEVELS
Sound power level
(1)
dB(A)
88
88
89
89
90
Sound pressure level - (10m)
(2)
dB(A)
56
56
57
57
58
DIMENSIONS
Length
mm
4000
4000
5000
6000
6000
Width
mm
2200
2200
2200
2200
2200
Height
mm
2550
2550
2550
2550
2550