1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
Relief Damper
Change'Air recommends the use of a relief damper assembly be
used in conjunction with all units installations unless balanced
powered exhaust is made available within the ventilated space.
Improper static pressure control of a ventilated space will affect the
ventilation capacities and unit performance.
A counter balanced, gravity relief damper assembly is available
through your Change'Air representative. This includes the relief
damper, an 8” depth wall sleeve, and an aluminum exterior louver.
A minimum finished wall depth
of 9.75" is required when the
relief assembly is used in
conjunction with the interior
grille in order for the damper to
operate freely.
Finished wall depths greater
than 8” may require a field
fabricated wall sleeve
extension.
Note: Locate the relief
damper assembly as far
away from the classroom
unit as possible within the
same ventilated space. Refer
to minimum clearances
when locating opening.
1. Cut or construct an
opening through the wall
adherent to the appropriate
size.
2. On the exterior, run a bead
of weatherproof caulking
around the perimeter of the
wall opening.
3. Insert the relief damper assembly into the wall opening from the
outside, with the louver blades pointing down and to the outside.
Securely fasten it to the wall through the standard 2” flange.
4. On the interior, seal or caulk between the wall sleeve and the
interior finished wall .
5. Once the ventilator is operating in an Occupied mode and using
proper balancing procedures, adjust the counter balance control
of the relief assembly by adding or removing weights as
necessary to relieve the required static pressure for that room.
6. Using screws and anchors, the melamine relief damper cover or
interior grille can now be installed to conceal the wall opening.
Rear Standoff (RSO)
Installation Note: When the vertical classroom unit is fitted with
a rear standoff (RSO) or rear plenum assembly (RPA) it becomes
necessary to fasten the unit to the wall by using a supplied 2” x
2” x 34” 18ga. Angle brace, that must be secured to the top
cover of the RSO assembly as described below.
We recommend the use of ¾” x #10 round head self-tapping
sheet metal screws to fasten the accessories to the unit.
Notice: You may require an assistant's help for this procedure.
Care should be taken to protect the painted finish when
handling the unit and accessories.
Owner’s Manual
10
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
1. On a clean, flat, unobstructed floor surface, lay out the pieces of
the standoff relative to the positions they are to be installed,
shown in the Installation/Assembly Drawings sent with the unit.
2. Clamp the angle brace so it is flush to the top, back edge of top
cover. Fasten the angle brace with four evenly spaced screws.
(This will be used at a later step to fasten the unit to the wall.)
3. Due to slight variations in the unit widths, it is best to assemble
the RSO on the unit rather than
preassembling the RSO and then fastening it to the unit.
4. Position the vertical classroom unit directly in front of its final
installation position. Allow enough room behind the unit for the
RSO and some room to work. (Once the RSO is mounted it may
become more difficult to relocate the unit.)
5. Place the Side Panel against the back of the unit in the
orientation shown and square up the corners and edges and then
securely fasten the panel to the unit using ½” x #10 round head
self-tapping sheet metal screws. Place screws through the 1”
front mounting flange of the standoff panel into the back of the
unit at approximately 18” apart or in the starting holes provided.
6. Repeat with opposite side panel.
7. Place top cover on top of the installed side panels with the angle
brace toward the wall side (rear) of the assembly. Square up the
corners and edges of both pieces and securely fasten the top
cover to the unit and to the top edge of each side panel
8. Place bottom cover in position between the installed side panels
along the floor. Square up the corners and edges of both pieces
and securely fasten the side panels to the bottom cover. Do not
mount the RSO to the unit through the top or bottom cover of the
standoff. (If this unit has packaged air conditioning these may
interfere with the removal of the exhaust fan during future service
maintenance.)
Top Plenum
1. Carefully unpack the plenum assembly. The plenums sent with
the units may vary in height or model, and will be labeled with a
CU# if provided.
2. Remove the front access covers from the appropriately selected
five-sided plenum assembly.
Fig. I