3. Wiring installation instruction

The Wiring diagram follows,the 

CWC 

01 connect to the AC Unit and KNX Power. 

Fig.3-2 

6

+ - 



AC unit 

MD-KNX-01 

 KNX TP-1
(EIB)bus

MAX 500m 

  

CWC 

01 is completely in conformity with EIB/KNX standard. ETS software  

      must be used by integrator to carry out configuration and project design.  
      For detailed information of ETS software, please contact knx association:  
      www.knx.org.     
 

  

ETS database 

*.vd*

of 

SYSCONTROL CWC 01

 consult our company

① 

Bus interface

Power supply DC 29V, 10mA  and connect to KNX bus

; 

② 

KNX programming button

press once to enter the programming mode,  

     press it again will exit. 

③ 

KNX programming statues  lamp

when it is light up means programming 

     status and can write data to the module by KNX bus 

④ 

RS485 communication ports

Communication port between KNX module  

     and indoor unit. 
 
 

 

Summary of Contents for CWC 01

Page 1: ...INSTALLATION MANUAL KNX gateway CWC 01 Thank you very much for purchasing our product Before using your unit please read this manual carefully and keep it for future reference ...

Page 2: ......

Page 3: ...recautions that should be brought to your attention during operation In order to ensure correct service of SYSCONTROL CWC 01 please read this manual carefully before using the unit For convenience of future reference keep this manual after reading it ...

Page 4: ...Table of Contents I Safety precautions 1 II Other precautions 3 III Installation procedure 5 IV ETS database group objects introduction 8 ...

Page 5: ...mproper handling may lead to personal death or severe injury Means improper handling may lead to personal injury or property loss Note 1 Harm means injury burn and electric shock which need long term treatment but need no hospitalization 2 Property loss means loss of properties and materials Warning arning Caution Caution Icon description Meaning lcon It indicates forbidding The forbidden subject ...

Page 6: ...l operation or heating which may result in fire CAUTION Do not install the unit in a place vulnerable to leakage of flammable gases Once flammable gases are leaked and left around the wire controller fire may occure The wiring should adapt to the wire controller current Otherwise electric leakage or heating may occur and result in fire The specified cables shall be applied in the wiring No externa...

Page 7: ...ting on the Wall M4X25 GB823 88 For Mounting on the Electrical Switch Box 6 7 3 2 1 No Name Qty Remarks SYSCONTROL CWC 01 Installation Manual For Mounting on the Wall Plastic screw bar Cross round head wood mounting screw Cross round head mounting screw 3 core shielded cable Plastic expansion pipe For fixing on the 86 electrician box For connecting the AC unit and MD KNX 01 1 Check whether the fol...

Page 8: ...ltage circuit Never connect it with a standard 220V 380V circuit or put it into a same Wiring Tube with the circuit 3 Do not attempt to extend the shield cable by cutting if it is necessary use Terminal Connection Block to connect 4 After finishing connection do not use Megger to have the insulation check to the signal wire 5 The default physical address of the CWC 01 is 15 15 255 If there are two...

Page 9: ...arameters 5 1 2 3 Dimensions Power supply No Name Remarks 85 51 16mm 29VDC 10mA Supplied through KNX bus LED indicator Push button KNX programming KNX programming button Configuration Configuration with ETS software 4 5 2 The product parameters ...

Page 10: ...project design For detailed information of ETS software please contact knx association www knx org ETS database vd of SYSCONTROL CWC 01 consult our company Bus interface Power supply DC 29V 10mA and connect to KNX bus KNX programming button press once to enter the programming mode press it again will exit KNX programming statues lamp when it is light up means programming status and can write data ...

Page 11: ...P 1 EIB bus Great flexibility of integration into your KNX projects Configuration is made directly from ETS the database of the device comes with a complete set of communication objects allowing from a simple and quick integration using the basic objects to the most advanced integration with monitoring and control all the AC unit s parameters Also available specific device s communication objects ...

Page 12: ...8 IV ETS database group objects introduction Fig 4 1 ...

Page 13: ...C Temp value ETS value The instruction as follow 0 set mode database type DPT_20 102 HVAC mode set value 0 Auto 1 Cool 2 Heat 3 Fan only 4 OFF 1 set temp database type DPT_9 001 temperature C 2 Set Fan speed data type DPT_5 001 percentage 0 100 Set value 0 auto 2 low speed 3 mid speed 4 high speed 3 Set Heat Cool mode data type DPT_1 100 heating cooling Set value 0 Cool mode 1 Heat mode 4 Set swin...

Page 14: ... 2 OFF 9 Fan swing status read data type DPT_1 002 boolean Read value 0 swing OFF 1 swing ON 10 Auxiliary Heater status read data type DPT_1 002 boolean Read value 0 Auxiliary Heater OFF 1 Auxiliary Heater ON 11 Indoor unit ambient temp read data type DPT_9 001 temperature C 12 Alarm state read data type DPT_1 005 alarm Read value 0 no alarm 1 alarm 14 ON OFF data type DPT_1 001 switch Set value 0...

Page 15: ...emperature increase and decrease data type DPT_1 007 step Set value 0 decrease 1 increase 22 Set Fan low speed data type DPT_1 002 boolean Set value 1 set as low speed 23 Set Fan medium speed data type DPT_1 002 boolean Set value 1 set as mid fan speed 24 Set Fan high speed data type DPT_1 002 boolean Set value 1 set as high fan speed 25 The fan speed circle setting data type DPT_1 007 step Set va...

Page 16: ...202000172630 Version SYSCONTROL CWC 01 MD14I 054BW ...