10
5: Set Auxiliary Heater ON/OFF; Data type: DPT_1.002 boolean.
Set value: 0-Auxiliary Heater ON; 1-Auxiliary Heater OFF.
This function is only available for heat mode.
6: Mode status read; data type: DPT_20.102 HVAC mode
Read value: 1-Cool mode; 2-Heat mode; 3-Fan mode; 4-OFF.
7: Set temperature read; data type: DPT_9.001 temperature(°C) .
8: Fan speed read; data type: DPT_5.001 percentage(0..100%).
Read value: 33%-low speed,67%-medium speed,100%-high speed,2%-OFF.
9: Fan swing status read; data type: DPT_1.002 boolean
Read value: 0-swing OFF,1-swing ON
10:Auxiliary Heater status read; data type: DPT_1.002 boolean.
Read value: 0-Auxiliary Heater OFF,1-Auxiliary Heater ON
11:Indoor unit ambient temp. read; data type: DPT_9.001 temperature(°C)
12:Alarm state read; data type: DPT_1.005 alarm
Read value: 0-no alarm; 1-alarm
14:ON/OFF; data type: DPT_1.001 switch
Set value: 0-OFF; 1-ON
15:Set auto mode; data type: DPT_1.002 boolean
Set value: 1-set as auto mode
16:set Cool mode; data type: DPT_1.002 boolean
Set value: 1-set as Cool mode
17:Set Heat mode; data type: DPT_1.002 boolean
Set value: 1-set as Heat mode