background image

Alarm settings

Def.setting

Set
value

Alarm settings

Def.setting Set value

1. Malfunction, supply fan

10. Moisture Deviation

Class

A

Class

Not

active

Delay

120 s

Delay

0 s

The unit stopped at alarm

No

The unit stopped at alarm

No

2. Malfunctinl, P1–heat,
HW-pump

(HW-units)

11. High inlet air temperature

Class

Not

active

Class

B

Delay

5 s

Delay

300 s

The unit stopped at alarm

No

The unit stopped at alarm

No

High inlet air

temperature

35°C

3. Malfunction, P1–cooling

(Cold water pump)

12. Low inlet air temperature

Class

Not

active

Class

A

Delay

5 s

Delay

300 s

The unit stopped at alarm

No

The unit stopped at alarm

No

Low inlet air

temperature

35°C

4. Filter guard

13. Inlet fan, upper limit

Class

B

Class

Not

active

Delay

180 s

Delay

0 s

The unit stopped at alarm

No

The unit stopped at alarm

No

5. Pressure sensor

14. Inlet fan, lower limit

Class

Not

active

Class

Not

active

Delay

5 s

Delay

0 s

The unit stopped at alarm

No

The unit stopped at alarm

No

6. External freeze guard

15. High room temperature

Class

Not

active

Class

Not

active

Delay

0 s

Delay

0 s

The unit stopped at alarm

No

The unit stopped at alarm

No

High room temperature

30°C

7. Fire alarm

16. Low room temperature

Class

A

Class

Not

active

Delay

0 s

Delay

0 s

The unit stopped at alarm

No

The unit stopped at alarm

No

Low room temperature

10°C

8. External switch

17. Overheating, electric heating

(Off on HW-units)

Class

C

Class

A

DVCompact

Commissioning Record

208384

5

Systemair AB

Summary of Contents for DVCompact

Page 1: ...DVCompact Supply Unit Commissioning Record Document in original language 208384 EN_GB 2013 12 11 A001...

Page 2: ...Contents 1 Commissioning Instructions 1 2 Commissioning Protocol 2...

Page 3: ...pped in different ways for example with water heater or electric heating coil The control unit is fitted with cables towed out of the unit Make sure that these cables are connected according to the sc...

Page 4: ...tory Function Temp Supply Room Supply Room Outside compensatory supply air temp Outside compensatory supply air temp Outdoor temperature compensation supply air Set point 21 0 C C Breakpoint 1 2 and 3...

Page 5: ...ormal and reduced fan speed is factory set as shown below Period 1 07 00 to 16 00 Monday to Friday normal fan speed 00 00 to 00 00 Saturday Sunday and holidays Period 2 00 00 to 00 00 Monday to Sunday...

Page 6: ...unning time 20 min min Activation Level Half speed 800 ppm Half speed ppm Full speed 1000 ppm Full speed ppm Difference below half speed fan stops 160 ppm Difference below half speed fan stops ppm Fir...

Page 7: ...let air temperature 35 C 4 Filter guard 13 Inlet fan upper limit Class B Class Not active Delay 180 s Delay 0 s The unit stopped at alarm No The unit stopped at alarm No 5 Pressure sensor 14 Inlet fan...

Page 8: ...Delay 5s Delay 0 s The unit stopped at alarm No The unit stopped at alarm No 21 Fire dampers 29 Cooling coil in manual mode Class Not active Class Not active Delay 0 s Delay 0 s The unit stopped at al...

Page 9: ...trol in manual model 33 Error on internal battery Class Not active Class A Delay 0 s Delay 0 s The unit stopped at alarm No The unit stopped at alarm No 26 Supply fan in manual mode Class Not active D...

Page 10: ...erves the right to make changes and improvements to the contents of this manual without prior notice Systemair AB Industriv gen 3 SE 739 30 Skinnskatteberg Sweden Phone 46 222 440 00 Fax 46 222 440 99...

Reviews: