EVC-RZHC-HUB_Room-Zone-HUB with cabinet_inst_GB_tbm_27.11.2019
1
09.12.19
Installation manual for
EVC-RZHC-HUB Room/Zone-Hub with cabinet
The room / zone hub is designed for the connection of a room controller,
two volume flow controllers with actuator LMVAX-D3-MOD, a CO
2
, VOC
or humidity sensor, a heating and cooling valve, a change-over sensor, a
presence detector and a condensation monitor or window contact.
The Hub module is used to supply power to the connected actuators and
sensors, as well as signal distribution. Factory-made, the hub is
delivered in a surface-mounted housing.
After removal from the housing, the base board is also suitable for
mounting on DIN rail
Dimensions (mm)
Technical data
Supply voltage
DC 48 V
Possible operating range
30 … 48 V DC
Power Consumption
4 W (without connected devices)
Operating temperature range
0 … +40°C
Relative humidity during operation
10 … 90% r.H., non-condensing
Storage conditions
-
20 … +40°C, non-condensing
Protection class
III safety extra-low voltage
Enclosure class
IP30 (IP00 without housing)
Mounting location
Wall or ceiling, switch cabinet
Mounting
Screw or DIN rail mounting
Weight
ca. 500 g
Dimensions with housing
160 x 140 x 65 mm
Dimensions without housing
110 x 100 x 40 mm
Electrical connection to master cabinet EVC-MC
1x RJ45, DC supply >30 V and Modbus RTU, network cable
type SF/UTP, min. Cat.5e, AWG 26/7, max.150 m, alt.
Network cable Type S/FTP, Cat.7,
AWG 23, max. 250 m