5/69 |
F-B90
Technical Parameters
Durability test
50 cycles/manually operated activation mechanism – with no change of the required properties
10000 + 100 + 100 cycles/actuator operated activation mechanism – with no change of the required properties
10000 cycles, actuator controlled for "SR" actuator (45 … 60 degrees rotation) - with no change of the required properties
Fire testing pressure
Underpressure up to 300 Pa
Safety position
Closed. (In fire scenario the damper closes via spring in actuator or spring in manual mechanism)
Airflow direction
Both directions
Allowed air velocity
Damper can still operate at max. 12 m/s. Air without any mechanical or chemical contamination
Side with fire protection
Depending on installation classification: From both sides (i <-> o)
Repeated opening
Suitable for daily check procedure. It is not possible to operate the device after reaching activation temperature.
Activation Temperature
Manually operated: 74 °C as standard by means of a spring after the melting of the thermofuse and/or after smoke sensor detection.
Actuator operated: 72 °C as standard by means of the spring after current interruption in the electro-thermal fuse and/or after smoke
sensor detection.
Operational temperature
Minimum: 0 °C
Maximum: 60 °C for 74 °C and 72 °C thermofuse
Environment suitability
Protected against weather disruptions, with temperature above 0 °C, up to 95% Rha, (3K5 according to EN 60721-3-3)
Open/Closed indication
Manually operated microswitches - Activation types H2
Actuator operated built-in microswitches - Activation types B230T/G230T up to BSD24T/GSD24T
Closing/Opening time
Manually operated < 10 s, actuator operated < 20 s
Inspection possibility
Types fitted with grille: through Grille. Inspection door for connection and actuator access. Types without grille connected from both
sides to duct: necessary to create inspection opening in the connected duct or attach removable or flexible part.
Maintenance
Not required. Dry cleaning if demanded by law in the country in which the dampers are installed.
Revisions
Determined by law in the country in which the fire dampers are installed but at least every 12 months.
Allowed pressure
1000 Pa
Blade tightness (STN EN 1751)
Class 3 as standard
Tightness of the housing (STN EN 1751)
Class C as standard
Conformity with EC directives
2006/42/EC Machinery Directive
2014/35/EU Low Voltage Directive
2014/30/EU Electromagnetic Compatibility Directive
Modulated Actuator
Can be set to any position when opening the blade - see types of activation mechanisms B24T-SR/G24T-SR
Driving actuator types
Summary of Contents for F-B90
Page 1: ...F B90 Multiblade Fire damper ...
Page 14: ...14 69 F B90 Dimensions Free area ...
Page 15: ...15 69 F B90 Dimensions ...
Page 16: ...16 69 F B90 Weights ...
Page 17: ...17 69 F B90 ...
Page 18: ...18 69 F B90 ...
Page 23: ...23 69 F B90 Types 00 01 02 installed in the wall Max EI90S ...
Page 24: ...24 69 F B90 ...
Page 28: ...28 69 F B90 Types 11 22 installed in the wall Max EI90S EI120 ...
Page 29: ...29 69 F B90 ...
Page 32: ...32 69 F B90 Types 00 01 02 installed in the wall Max EI90S ...
Page 33: ...33 69 F B90 ...
Page 37: ...37 69 F B90 Types 11 22 installed in the wall Max EI90S EI120 ...
Page 38: ...38 69 F B90 ...
Page 41: ...41 69 F B90 Types 00 01 02 installed in the wall Max EI90S ...
Page 44: ...44 69 F B90 Types 11 22 installed in the wall Max EI90S EI120 ...
Page 47: ...47 69 F B90 ...
Page 48: ...48 69 F B90 ...
Page 49: ...49 69 F B90 ...
Page 61: ...61 69 F B90 Operation manual ...
Page 62: ...62 69 F B90 ...
Page 63: ...63 69 F B90 ...
Page 64: ...64 69 F B90 ...
Page 66: ...66 69 F B90 ...
Page 69: ...Systemair DESIGN 2020 10 07 HandBook_F_B90_en GB 1D2E1FF0 E010 11EA E8DD 8BBB7258CB9B ...