46/48 |
FDR-3G…OF
Operation manual
Warning
To avoid injury, make sure to wear gloves and keep the blades movement area clear while manipulating with the
damper.
Fire Damper Functionality Check
Manually Operated Activation Mechanism
Open the damper - turn the red crank (P10) using a hexagon bent wrench No. 10 (P13). Turn the red crank so that the
indicator arrow is pointing to the “OPEN“ position (P11), the red crank needs to remain in the “OPEN“ position, and the
microswitch for the open position indication must be pushed (if installed).
Close the damper – release the mechanism by pressing the red release button (P9), the red crank will adjust its
indicator arrow pointing to the “CLOSED“ position (P12) and remain locked in this position, the microswitch for the
closed position indication must be pushed (if installed).
Open the damper - turn the red crank (P10) using a hexagon bent wrench No. 10. (P13) Turn the red crank so that the
indicator arrow is pointing to the “OPEN“ position, the red crank needs to remain in the “OPEN“ position, and the
microswitch for the open position indication must be pushed (if installed).
Spring Return Actuator Operated Activation Mechanism
The fire damper must open automatically after the actuator circuit closes – the arrow on the actuator axis must show
the position 90°.
Press the control switch (P9) on the Thermoelectric fuse and hold it until the fire damper is fully closed – the arrow on
the actuator axis must show the position 0°.
Release the control switch on the Thermoelectric fuse. The fire damper must become fully open – the arrow on the
actuator axis must show the position 90° - which is the operating position.
Smoke detector and spring return actuator operated activation mechanism
The fire damper must open automatically after the actuator circuit closes – the arrow on the actuator axis must show
the position 0°.
Press the control switch (P9) on the Thermoelectric fuse and hold it until the fire damper is fully closed – the arrow on
the actuator axis must show the position 90°.
Release the control switch (P9) on the Thermoelectric fuse. The fire damper must now open automatically.
Press the control switch on the smoke sensor and hold it until the fire damper is fully closed. Or use a smoke spray for
sensor testing and spray into the grille directly onto the smoke detector. Check if the fire damper will fully close. After a
while the smoke detector will clear itself from the testing spray and the damper will open again.
Release the control switch on the Thermoelectric fuse. The fire damper must become fully open – the arrow on the
actuator axis must show the position 0° - which is the operating position.
Operation Manual
After installation, it is necessary to adjust the damper into its operating position – open the fire damper.
Spring Return Actuator Operated Activation Mechanism
Connect the electric driving mechanism to the relevant electric power supply (see Electrical connection section). The
electromotor is activated and adjusts the damper into its open position.
Manually Operated Activation Mechanism
Turn the red crank into the “OPEN“ position. The damper blade must remain in open position.
Damper Inspection
The activation mechanism keeps the dampers on stand-by during their entire life cycle in accordance with this manual
issued by the manufacturer. It is not permitted to alter the dampers in any way nor perform any changes to their
structure without the manufacturer’s consent.
Summary of Contents for FDR-3G
Page 1: ...FDR 3G OF Overflow Fire Damper FDR 3G ...
Page 5: ...5 48 FDR 3G OF AM FD Activation Mechanisms CBR FD Cover Boards ...
Page 9: ...9 48 FDR 3G OF P15 Grid P16 Extended ductwork ...
Page 13: ...13 48 FDR 3G OF Dimensions Free area Dimensions Note 3 Inclusive bearing Overhangs Weights ...
Page 15: ...15 48 FDR 3G OF ø 250 DN ø630 Standardardly in position B On demand in position L T ...
Page 19: ...19 48 FDR 3G OF ...
Page 20: ...20 48 FDR 3G OF ...
Page 23: ...23 48 FDR 3G OF ...
Page 24: ...24 48 FDR 3G OF ...
Page 27: ...27 48 FDR 3G OF ...
Page 28: ...28 48 FDR 3G OF ...
Page 31: ...31 48 FDR 3G OF ...
Page 32: ...32 48 FDR 3G OF ...
Page 48: ...Systemair DESIGN 2020 10 23 HandBook_FDR_3G_OF_en GB 8519DCD0 0720 11EB DCA1 21ABDD8D93BC ...