| Instructions for unloading on the site as well as installation and connection
I.2.10.3 Heating coil — hot water
If the heating coil is mounted on the rigid duct connection of the air handling unit, the installer must support the coil fur-
ther by brackets or suspension prior to mounting of ducts and pipes. Duct as well as heating coil must be insulated ac-
cording to local guidelines.
I.2.10.4 Heating coil — electrical
Duct as well as heating coil must be insulated according to local guidelines.
I.2.10.5 Change-over coil for water or refrigerant — heating and cooling
If the change-over coil is mounted on the rigid duct connection of the air handling unit, the installer must support the
coil further by brackets or other suspension. Under the coil the integrated tray for collection of condensate is insulated
with 15 mm of Armaflex. Ducts as well as change-over coil must be insulated according to local guidelines.
Note! Instal-
lation of water trap is very important. See the description of water trap in this User Manual.
I.2.10.6 Cooling coil for chilled water or refrigerant
If the cooling coil is mounted on the rigid duct connection of the air handling unit, the installer must support the coil fur-
ther by brackets or suspension. Under the coil the integrated tray for collection of condensate is insulated with 15 mm
of Armaflex. Duct as well as heating coil must be insulated according to local guidelines.
Note! Installation of water trap
is very important. See the description of water trap in this User Manual.
I.2.10.7 Attenuators for installation in ducts
The duct connection is available with 20 mm or 30 mm flange for LS profile and screw clamps. Furthermore always a
8,5 mm hole in each corner of the flange. If the attenuator is mounted on the rigid duct connection of the air handling
unit, the installer must support the attenuator further by brackets or suspension. Ducts as well as attenuators must be
insulated according to local guidelines.
I.2.11
Refitting of safety guards
The guard is a safety guard installed inside the door.
Note! The safety guard shown on the illustration below is option-
al from Systemair and must be ordered separately.
According to Machinery Directive guidelines, tools are necessary
for the removal of the guard. If the guard has been demounted during the installation on the site, the guard must be re-
fitted before startup of the unit.
If the optional guard from Systemair has not been ordered, the installer, that starts-up the unit, must make and install a
guard, where a guard is demanded according to Machinery Directive guidelines.