Speed control for rotary heat exchanger |
5-5
The sensor is installed to the right seen from the
inspection side of the unit. Check that collision between
sensor and rotor is impossible. Adjust position of sensor if
necessary.
Check the illustrated screw on the rotor for activation of
signal from the sensor.
Note:
The distance from the screw to the sensor
must
not
exceed 2 mm.