background image

Systemair NOVA drive 370

|  

13

Error

Blinks

Retries

Flag bit

Value in AlarmLog

Rotary guard

Always on


(no auto reset)

8

9

Overcurrent stop

1

2

0

1

Overvoltage

2

2

1

2

Undervoltage

3

1

2

3

Hardware error (gate kill)

4

1

3

4

Modbus communication

5

Unlimited

15

15

Overheating stop

6

1

4

5

Backend communication

7

0

5

6

CRC error

8

0

7

8

Table 9 – Summary of errors

9 NOVA drive features

9.1 

Rotary guard

Rotary guards counts the time in between pulses given by the rotary guard sensor. The time is compared against the 
maximum allowed time which is calculated based on the inverter speed. The time allowed at maximum speed given by 
the dip switches is 12 seconds to permit 2 full rotations (2x5 seconds) and 2 extra seconds of tolerance.

When the rotary guard passes the rotary sensor an LED sequence is played (red-green-red-green). This will play even 
if the inverter output is stopped.

The rotary guard sensor is connected to the Uout (10V), 0V and RUN, to give the signal to NOVA. See Figure 10 for the 
connection diagram.

Rotary guard is by default enabled and will eventually stop (coast) the Motor if the pulse is not detected for enough 
time. At this point the inverter will attempt to start again up to 3 times, after which it will stop.

It is possible to disable the rotary guard feature by connecting the RUN input (Rotary guard) to Uout (10V). Refer to 
Figure 9 for a diagram. When the inverter is running the motor and the rotary input is high for more than 10 seconds 
the functionality is disabled. At this point a power reset is needed, to enable it again.

9.2 Purge function

When the inverter has been stopped for 30 minutes the purge function is activated. During purge the inverter will start 
the motor and set it to run at 10 rpm for 12 seconds. After this time the inverter is stopped again. The sequence is 
repeated after 30 minutes of inactivity.

9.3 Brake functionality

If dip switch 4 is set to ON the brake functionality is activated. When the motor is stopped and if the brake functionality 
is activated it will brake the rotor by shorting the windings. With brake activated it is harder to move the rotor, when 
stopped. If brake functionality is activated it can take up to 10 seconds to start braking once the motor is stopped.

9.4 Direction input

It is possible to use the direction input to change the direction the motor is spinning. If nothing is connected, the direc-
tion input is pulled high. To reverse the direction connect the direction input to 0V. Refer to (B) in Figure 11 for a con-
nection diagram.

Note that direction will not change once the motor is running.

9.5 Automatic test

Activate dip switch 5 for more than 10 seconds to start the automatic test. During automatic test the motor will go to 
maximum speed and wait there for 10 seconds. After this it will ramp down and stop for another 10 seconds. The pro-
cess is repeated again and again, until stopped by setting the dip switch 5 off.

Summary of Contents for NOVA drive 370

Page 1: ...Systemair NOVA drive 370 Product Description...

Page 2: ...have a minimum shaft speed of 0 2rpm By external gear wheel it can run exchangers from 0 02 20rpm Control signal 0 10V Modbus RTU have an un linear function to ensure a linear heat transfer Extract su...

Page 3: ...Product description 4 3 Environmental constraints 4 4 Technical data 5 5 Mechanical and electrical installation 7 6 Motor parameters 11 7 LED behaviour 12 8 Fault behaviour 12 9 RHC features 13 10 Mo...

Page 4: ...the electrical installation on the rating plate matches the power supply Please refer to Table 2 for maximum fuse ratings and type CAUTION Risk of hot surfaces and electric shock if the unit has been...

Page 5: ...utral or phase to phase earth ground Frequency Hz 50 Hz 2 Hz Max input current 230V supply Arms 3 6 External input fuse size Type MAX C16 Minimum supply without speed reduction Vrms 207 Minimum supply...

Page 6: ...RS485 24V protected Control interface alarm 1x Alarm relay NC C NO Maximum 2A 250Vac or 6A 24Vdc Indicators Red Green Yellow LED on the PCB check Figure 6 for position Settings Dipswitch for Motor se...

Page 7: ...entation shall be vertical with the cable glands facing downwards This is to ensure the best thermal performance of the product For reference please refer to Figure 2 Figure 2 Mounting orientation of...

Page 8: ...Motor U V W Supply N L Alarm NC COM NO Solid wire 1 2 0 2 4 0 mm2 26 12 AWG Stranded wire 1 0 2 2 5 mm2 26 14 AWG Flat blade max 3 5 mm Analogue Control 0V Uin Uout Rotary Sensor 0V RUN DIR MODBUS 0V...

Page 9: ...ing Grounding hazard For the operator safety it is important to ground the drive properly and follow the provided grounding guidelines RCD compatibility For extra safety protection a Residual Current...

Page 10: ...anner until power is reset Enable rotary guard To use the rotary guard the sensor must be supplied with 10 V from Uout 10V and connected to ground 0V The out put from the sensor must be connected to R...

Page 11: ...if you wish to change the direction the motor rotates Note that the direction will change the next time the motor starts not when it is already rotating Maximum speed can be reduced and set as 50 100...

Page 12: ...how the latest error as it has higher priority Rotary guard Rotary guard passed When the rotary guard passes it shows the red green red green sequence 200ms each LED If the inverter has no warnings or...

Page 13: ...9 for a diagram When the inverter is running the motor and the rotary input is high for more than 10 seconds the functionality is disabled At this point a power reset is needed to enable it again 9 2...

Page 14: ...owing Modbus registers are available All the registers are either input registers 16 bit read only denoted by R or holding registers 16 bit read write denoted by RW Register Address Type Description B...

Page 15: ...rd in 0x115 R Rotor guard value 0 or 1 Test running 0x116 R 1 when test is running 0 otherwise Speed external 0 10V 0x117 R 0 4095 speed input Trimmer 0 10V 0x118 R 0 4095 trimmer input Extended SW ve...

Page 16: ...Safety req Automatic electrical controls for household and similar use EN 60335 2 40 2004 A11 2014 A12 2005 Safety req Particular requirements for electrical heat pumps air conditioners and dehumidifi...

Page 17: ...286rpm Current 0 79 0 46A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 2 8 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation...

Page 18: ...ent 1 37 0 79A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 5 5 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation direction...

Page 19: ...rent 2 04 1 18A Pole pairs 14 Rated Speed 214 3 rpm Speed Range 0 4 286 214 rpm Rated Torque 8 N m Back Electromotive Force 214 rpm V Rotor inertia 0 5 0 25Kg cm Connection mode Y Rotation direction C...

Page 20: ...no www systemair no Systemair B V Zanddonkweg 7a 5144 NX Waalwijk NETHERLANDS Tel 31 0 85 00 66 200 info systemair nl www systemair nl Systemair HVAC Spain S L U C Montecarlo 14 Fuenlabrada ES 28942...

Reviews: