37
English
8 - Technical Data
Heating
Indoor Unit
PAW-250W5APAC
Outdoor Unit U-250PZH2E8
Item
Symbol
Value
Unit
Item
Symbol
Value
Unit
Rated heat output
Design load for heating
Prated
(Pdesign)
21
kW
Seasonal space heating energy
efficiency
η
s,h
178
%
Declared capacity for heating for part load at
LWT = 45°C and outdoor temperature Tj
Declared COP for part load at
LWT = 45°C and outdoor temperature Tj
Tj = -7
℃
Pdh
18,13
kW
Tj = -7
℃
COP
2,90
- or %
Tj = +2
℃
Pdh
11,04
kW
Tj = +2
℃
COP
4,13
- or %
Tj = +7
℃
Pdh
7,10
kW
Tj = +7
℃
COP
6,39
- or %
Tj = +12
℃
Pdh
6,19
kW
Tj = +12
℃
COP
8,96
- or %
Tj = bivalent temperature
Pdh
20,50
kW
Tj = bivalent temperature
COP
2,08
- or %
Tj = operation limit
temperature
Pdh
15,20
kW
Tj = operation limit
temperature
COP
1,72
- or %
Tj = -15
℃
(if TOL is < -20
℃
)
Pdh
-
kW
Tj = -15
℃
(if TOL is < -20
℃
)
COP
-
- or %
Bivalent temperature
Tbiv
-10
℃
Operation Limit temperature
TOL
-20
℃
Degradation co-efficient
Cdh
0,90
-
-
Power consumption in modes other than active mode
-
Off mode
POFF
0,028
kW
Thermostat off mode
PTO
0,130
kW
Standby mode
PSB
0,028
kW
Crankcase heater mode
PCK
0,009
kW
Other Items
Other Items
Sound power level (outdoor)
LWA
49 / 82
dB
Rated air flow rate, outdoors
-
9.600
m
3
/h
Emission of Nox
Nox
-
mg/kWh
-
Annual (eletrical) energy
consumption
QHE
9.379
kWh