background image

4 / 8    |    PP-87_201701    |    PKIR-E60S & EKIR-E60S

2 Operation manual

After installing the damper the actuator needs to be set up into 

emergency position, meaning that the fire/evacuation damper 

blade will open/close. The control system which the damper is 

connected to signals (according to the damper connection) opens 

or closes the damper blade.

2.1 Electrical actuator

Connect the electrical actuator to power (see wiring schemes) 

and the electromotor is activated and puts the damper into ope-

rating position.

Fig. 3: Wiring scheme of actuators BELIMO BLF230-T (BFL and 

BFN instead of BLF), BFL230-T, BFN230-T, BF230-T

Fig. 4: Wiring scheme of actuators BELIMO BFL24-T-ST, BFN24-T-

ST, BF24-T-ST

Fig. 5: Wiring scheme of actuator BELIMO BFL24-T, BFN24-T, 

BF24-T

Damper Parts Description: 

see Fig. 1

Fig. 2: Horizontal installation of the PKIR-E60S and EKIR-E60S

4

3

2

1

ØD+60

ØD

ØD+100

ØD+X

0-1500

5

mastic (Intumex AN)

to seal (Intumex AN)

mastic (Intumex AN)

1.2 Horizontal installation of the PKIR-E60S  

(in a vertical duct – Fig.2)

It is the same procedure as in 1.1 Vertical installation... (on the 

figure 2 there is only dry method)

Note

•  Caution: Main power supply voltage!
•  A device that disconnects the pole conductors 

(minimum contact gap 3 mm) is required for iso

-

lation from the power supply.

•  Parallel connection of several actuators possible. 

Power consumption must be observed!

!

S1 S2 S3 S4 S5 S6

 <5°

 <80°

2

1

N L1

BAE or BAT

Tf1

Tf2

Tf3 LED

Connecting lead with plugs for linking to the communication

                  and power units

S1 S2 S3 S4 S5 S6

 <5°

 <80°

2

1

T

~

BAE or BAT

Tf1

Tf2

Tf3 LED

Note
•  Supply via safety isolation transformer

•  Parallel connection of several actuators possible. 

•  Power consumption must be observed!

!

S1 S2 S3 S4 S5 S6

 <5°

 <80°

2

1

– + 

T

~

BAE or BAT

Tf1

Tf2

Tf3 LED

1

2
3

4

5

9

Summary of Contents for PKIR-E60S

Page 1: ...IR E60S and EKIR E60S Round Fire and Evacuation Damper INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EACH FIRE EVACUATION DAMPER MUST BE INSTALLED ACCORDING TO THIS INSTALLATION MANUAL 1396 CPD 0069 ...

Page 2: ...driving mechanism as standard They are intended for installation in places which are protected against weather disruptions in the ducts distributing air without any mechanical or chemical contamination in the following operating conditions Maximum air flow velocity 12 m s Temperature within the range 10 up to 60 C From the noise perspective all Systemair dampers are passive Increased noise can onl...

Page 3: ...nstallation of the PKIR EI60S in a horizontal duct Fig 1 1 Insert the fire damper into the duct the sealing spiro safe must be wholy in the duct and the end of the fire damper has to be ca 5 mm away from the ridge to allow for thermal dilatations The distance between the end of the damper and the wall can be L 0 1500 mm 2 Seal both gaps between ends of the damper and the duct with fire resistant m...

Page 4: ...Fig 1 Fig 2 Horizontal installation of the PKIR E60S and EKIR E60S 4 3 2 1 ØD 60 ØD ØD 100 ØD X 0 1500 5 mastic Intumex AN to seal Intumex AN mastic Intumex AN 1 2 Horizontal installation of the PKIR E60S in a vertical duct Fig 2 It is the same procedure as in 1 1 Vertical installation on the figure 2 there is only dry method Note Caution Main power supply voltage A device that disconnects the pol...

Page 5: ...his depends on operation temperature The position of the blade is possible to check visually through the inspection lid or the blade position is signalized by the control system which the damper is connected to Damper must close open also at any interruption of electricity supply when the damper blade is moved by the energy of the actuator s return spring 5 Warranty Conditions For warranty conditi...

Page 6: ...te of the following inspection after deficiencies elimination Inspection technician s signature Periodic damper inspections at least once in 12 months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature Operation Journal ...

Page 7: ...R E60S PP 87_201701 7 8 Periodic damper inspections at least once in 12 months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature ...

Page 8: ... resistance maintenance of the cross section under E integrity E E60 ve ho i o S insulation I smoke leakage S mechanical stability under E cross section under E Durability of response delay sensing element response temperature and load bearing capacity Pass Durability of operational reliability open and closing cycle Pass Damper Identification Building object Emplacement Room no Position no Identi...

Reviews: