background image

PKIR-E60S & EKIR-E60S

    

|    PP-87_201701    |    5 / 8

Operational conditions

The actuator keeps the fire dampers in operation and in safe 

status during their whole period of service. It is not permitted 

to change or modify the dampers and any damper parts cannot 

be removed without the manufacturer’s permission. The opera-

tor regularly checks the dampers according to instructions and 

norms given in the country.

If not stated otherwise the operator does the damper check once 

every 12 months. Damper checking is to be done by an autho-

rized person. The damper status determined during the check is 

noted into the operation diary with the date of the check, name, 

last name and signature of the person that has done the check. If 

any inadequacies are determined it is necessary to note a propo-

sal for their elimination into the operation diary.

During a visual check visible damages to the damper parts are 

also to be checked. From the outer side of the damper check the 

damper casing and actuator. During a visual check from the inner 

part of the damper, the inspection lid is dismounted and the 

sealing is checked together with the intumescent material. Check 

the damper inner casing, thermo-electrical release device, all the 

sealings inside the damper, damper blade and also the correct-

ness of the damper blade closure (when it is at the end stop in 

closed position). The damper blade must be open in operation 

mode. 

Do not open the inspection lid in the event of airflow in 

the ductwork! 

3 Fire Damper Functionality Check

The damper function is checked when the switch on the ther-

mo-electrical release device is pressed and held as shown in Fig. 

6. With the switch you simulate a failure of the thermal electrical 

release device. It is necessary to hold the switch in ON mode 

during the whole damper function check. The actuator puts 

the damper into emergency position – it closes/opens the fire/

evacuation damper blade with the energy of return spring of 

the actuator. The damper should close/open within about 20-30 

seconds (this depends on operation temperature). The position 

of the blade is possible to check visually through the inspection 

lid or the blade position is signalized by the control system which 

the damper is connected to.

Damper must close/open also at any interruption of electricity 

supply when the damper blade is moved by the energy of the 

actuator’s return spring.

5 Warranty Conditions

For warranty conditions ask please our Systemair colleagues in 

your country.

Before you can install the fire damper, it‘s functionality must be 

tested as per chapter 3 (Fire Damper Functionality Check).

DO NOT INSTALL NON-FUNCTIONING FIRE DAMPERS!

Changes of fire damper functionality, caused by transport or 

installation, aren‘t reclaimable after installation (deformations, 

damages, mechanical damage of the sealing material, foreign 

objects which can constrain the blade movement, wrong hand-

ling of the activating mechanism etc.)

Before you can connect the fire damper into the ductwork, the 

fire damper functionality must be checked again (according to 

chapter 3, in Fire Damper Functionality Check).

4 Damper inspection

During the check the damper should be in operational mode, 

meaning that during the visual check the fire/evacuation damper 

blade is open/closed. Correct functioning of the actuator release 

is checked by holding the switch on the thermo-electrical release 

device. Closing/opening of the damper is provided by the spring. 

After the function check put the damper into operation mode by 

releasing the switch on the thermo-electrical release device.

Recommended checks according to the EN 15 650 regulation:

1.  date of inspection
2.  check of the end switch’s connection for damage, if appli-

cable

3.  check for damper cleanliness and clean if needed
4.  check the blades and sealing, correction and record if 

needed

5.  check the fire damper’s safe closure – for details please see 

the previous section

6.  check if the damper moves while in its open and closed 

position, correct and record if needed

7.  check the end switch indicating the open and closed positi-

on, correct and record if needed

8.  check if the damper is in its standard position.

Switch

Fig. 6: Electro-thermal fuse - control switch

BAE

actuator BF

BAT

actuator BFL and BFN

Summary of Contents for PKIR-E60S

Page 1: ...IR E60S and EKIR E60S Round Fire and Evacuation Damper INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS EACH FIRE EVACUATION DAMPER MUST BE INSTALLED ACCORDING TO THIS INSTALLATION MANUAL 1396 CPD 0069 ...

Page 2: ...driving mechanism as standard They are intended for installation in places which are protected against weather disruptions in the ducts distributing air without any mechanical or chemical contamination in the following operating conditions Maximum air flow velocity 12 m s Temperature within the range 10 up to 60 C From the noise perspective all Systemair dampers are passive Increased noise can onl...

Page 3: ...nstallation of the PKIR EI60S in a horizontal duct Fig 1 1 Insert the fire damper into the duct the sealing spiro safe must be wholy in the duct and the end of the fire damper has to be ca 5 mm away from the ridge to allow for thermal dilatations The distance between the end of the damper and the wall can be L 0 1500 mm 2 Seal both gaps between ends of the damper and the duct with fire resistant m...

Page 4: ...Fig 1 Fig 2 Horizontal installation of the PKIR E60S and EKIR E60S 4 3 2 1 ØD 60 ØD ØD 100 ØD X 0 1500 5 mastic Intumex AN to seal Intumex AN mastic Intumex AN 1 2 Horizontal installation of the PKIR E60S in a vertical duct Fig 2 It is the same procedure as in 1 1 Vertical installation on the figure 2 there is only dry method Note Caution Main power supply voltage A device that disconnects the pol...

Page 5: ...his depends on operation temperature The position of the blade is possible to check visually through the inspection lid or the blade position is signalized by the control system which the damper is connected to Damper must close open also at any interruption of electricity supply when the damper blade is moved by the energy of the actuator s return spring 5 Warranty Conditions For warranty conditi...

Page 6: ...te of the following inspection after deficiencies elimination Inspection technician s signature Periodic damper inspections at least once in 12 months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature Operation Journal ...

Page 7: ...R E60S PP 87_201701 7 8 Periodic damper inspections at least once in 12 months Date Description of found defects and date of the following inspection after deficiencies elimination Inspection technician s signature ...

Page 8: ... resistance maintenance of the cross section under E integrity E E60 ve ho i o S insulation I smoke leakage S mechanical stability under E cross section under E Durability of response delay sensing element response temperature and load bearing capacity Pass Durability of operational reliability open and closing cycle Pass Damper Identification Building object Emplacement Room no Position no Identi...

Reviews: