19
GB
Function
Preset value
Set value
Frost Protection
Mode (EL unit Off):
On
On
Off
Frost limit temperature:
See Alarm settings/
Low frost guard temp
See Alarm settings/
Low frost guard temp
Set point when stopped:
(return water)
10. °C
°C
P-band when running:
5.
Pressure Input
Supply/Exhaust Air Fan
Supply Air Fan Pressure at 0V
Supply Air Fan Pressure at 10V
Exhaust Air Fan Pressure at 0V
Exhaust Air Fan Pressure at 10V
0. (Pa)
CAV 1600 Pa VAV 500 Pa
0. (Pa)
CAV 1600 Pa VAV 500 Pa
(Pa)
(Pa)
(Pa)
(Pa)
Night cooling
Mode:
Off
On
Off
Run when day outdoor temp is
higher than:
22. °C
°C
Stop when night outdoor temp is
higher than:
15. °C
°C
Stop when night outdoor temp is
lower than:
5. °C
°C
Stop when room temp is lower
than:
18. °C
°C
Cool Recycling
Mode:
Off
On
Off
Start Limit:
2. °C
°C
Control On Demand
Min time for control on demand:
60. min
min
Support control:
Off
On
Off
Run Exhaust Air Fan when support
control active
On
On
Off
CO2 control
Off
On when active time channel
On when in-active time channel
On
Off
On when active time channel
On when in-active time channel
On
CO2 control Type
Damper
Fan
Damper
Fan