6/48 | User Manual S-BM2 | 202010
Installation Methods
S-BM2 Smoke control dampers are CE certified following the Construction Products Regulation according to EN 12101-8:2011.
Tested according to EN 1366-10:2011 + A1:2017, EN 1366-2:2015 and classified according to EN 13501-4:2016.
The smoke control damper together with its installation form an inseparable part of the fire resistivity rating.
Tab. 1: Fire resistivity of S-BM2 - wall mounted
Dimension
Range
(mm)
Classification
Supporting
Cons
truction
Construction Type/Minimal Thickness (mm)
Allowed
Blade Axis
Orientation
Wet
Dry
Fit
200 × 425
up to
1000 × 1225
EI90 (v
ew
i ↔ o) S1000 C
mod
MAmulti
Wall
Rigid/125
Flexible/125
EI90 (h
ow
i ↔ o) S1000 C
mod
MAmulti
Floor/
ceiling
-
EI120 (v
ew
i ↔ o) S1000 C
mod
MAmulti
Wall
Rigid/125
Flexible/125
EI120 (h
ow
i ↔ o) S1000 C
mod
MAmulti
Floor/
ceiling
-
Dimension
Range
(mm)
Classification
Duct Orien
ta
tion
Applicable Duct Tested per Standard
Allowed
Blade Axis
Orientation
In the Duct
On the Duct/
Bottom Mounted
On the Duct/
Top Mounted
On the Duct/
Side Mounted
200 × 425
up to
1000 × 1225
EI90 (v
ed
i ↔ o) S1000 C
mod
MAmulti
Horizontal
duct
EN 1366-9,
EN 1366-8
EN 1366-9,
EN 1366-8
EI90 (h
od
i ↔ o) S1000 C
mod
MAmulti
Vertical
duct
-
EI120 (v
ed
i ↔ o) S1000 C
mod
MAmulti
Horizontal
duct
EN 1366-9,
EN 1366-8
EI120 (h
od
i ↔ o) S1000 C
mod
MAmulti
Vertical
duct
-
Tab. 2: Fire resistivity of S-BM2 - duct mounted