Main menu item
Sub-menu item 1
Sub-menu item 2
Explanations
P1–Cooling
Auto
Set the pump control for the
cooling coil to
Auto
,
On
or
Off
Fire damper
Auto
Set the Fire damper to
Auto
,
Open
or
Close
Note:
Needs to be activated in order
to be visible here
Configuration of fire damper
functions are made at
System
level
Outdoor air
damper
Auto
Set
the Outdoor air damper to
Auto
,
Open
or
Close
→
Settings
In this menu group the settings
for the activated functions are
available. Depending on which
choices have been made in the
configuration menu some of the
possible alternatives may not
be displayed.
→
Control temp
Supply air
control
P-band:
33.0°C
I-time:
100.0
sec
Set
P-band and I-time for the
Supply air control function
Note:
See Corrigo E ventilation
manual for deeper explanation
Room control
P-band:
100.0°C
I-time:
300.0
sec
Set
P-band and I-time for the
Room control function
Note:
See Corrigo E ventilation
manual for more info
Shutdown mode
P-band:
100.0°C
I-time:
100.0
sec
Set
P-band and I-time for the
Shutdown function
Note:
See Corrigo E ventilation
manual for deeper explanation