4.4.1 Installation procedure
1
Prepare the surface where the unit is to be mounted. Make sure that the surface is flat, levelled and that
it supports the weight of the unit. Perform the installation in accordance with local rules and regulations.
2
Lift the unit in place.
Warning
Beware of sharp edges during mounting and maintenance. Make sure that a proper lifting device is
used. Use protective clothing.
3
Level the unit with help of the enclosed mounting
feet
4
Connect the unit electrically to the mains through
the all pole circuit breaker (safety switch), which is
enclosed inside the unit on delivery. The wiring is
led through the top of the unit.
See enclosed wiring diagram, and below table for
more information.
Warning
The units electrical connection to the mains
supply must be preceded by an all pole circuit
breaker with a minimum 3 mm gap.
Danger
• Make sure that the Mains supply to the
unit is disconnected before performing any
maintenance or electrical work!
• All electrical connections must be carried out
by an authorized installer and in accordance
with local rules and regulations.
Installation instructions
207575
11
Systemair Sverige AB