Topvex SR07, SR09, SR11 E
Installation instruction
205870
Systemair AB
10
Dimension and Weight
Dimension and weight See
fig. 1.
Handle and hinges are removable.
Inspection doors can open without handle by using a 16mm cap key.
Transport and storage
The Topvex should be stored and transported in such a way that it is protected against physical
damage that can harm panels, handles, display etc. It should be covered so that dust, rain and snow
cannot enter and damage the unit and its components. The unit is delivered in one piece containing all
necessary components, wrapped in plastic on a pallet for easy transportation. If separation is required,
please refer to section headed "Separation of the appliance".
The appliance may be lifted using a forklift truck
or be elevated using metal tubes inserted
through the holes in the feet and suspended by
soft cables. If possible secure the ends of the
metal bars and cables. To avoid collapse of the
unit’s feet, do not try to slide the unit
into place after it has been put down on the
ground.
Where/how to Install
The unit is meant for horizontal installation. The
electronic components should not be exposed to
lower temperature than 0°C or higher than
+50°C.
When mounting; make sure to leave enough
space to access the service doors. See
fig.1
for
measurement requirements.
General maintenance includes replacing the filters and removing fan motors inside the unit for
cleaning and cleaning the heat exchanger inside the unit.
Avoid placing the unit against a wall, as low frequency noise can cause vibrations in the wall.
The outdoor air intake of the building should if possible be put in the northern or eastern side of the
building and away from other exhaust outlets like kitchen fan outcasts or laundry room outlets. The
extract air should ideally be led out via a roof cowl away from any outdoor air intakes, windows,
balconies etc.
Note!
If the handles are used, the required safety for the unit is only reached if the handles are locked
and the keys kept in a secure place during operation.
The unit must be duct connected or in some other way provided with protection so that it is not
possible to come in contact with the fans through the duct connections.