6
5
Transport and storage
The Topvex SoftCooler should be stored and transported in such a way that it is protected against physical damage that
can harm panels, handles etc. It should be covered so that dust, rain and snow cannot enter and damage the unit and
its components. The appliance is delivered in one piece containing all necessary components, wrapped in plastic on a
pallet for easy transportation.
When transporting the Topvex SoftCooler use a forklift, but once installed on the floor avoid transfer, the feet can dam-
aged due to lateral loading.
Warning
• The unit is heavy. Be careful during transport and mounting. Risk of injury through pinching. Use
protective clothing.
• Be careful so the unit doesn't tip over.
6
Installation
6.1
Unpacking
Verify that all ordered equipment are delivered before starting the installation. Any discrepancies from the ordered
equipment must be reported to the supplier of Systemair products.
6.2
Where/how to install
Topvex SoftCooler are meant for indoor installation. Place the unit on a
horizontal flat surface
. It’s important that the
unit is completely levelled before it is put into operation.
The electronic components should not be exposed to lower temperature than 0° C and higher than +50° C.
The following max. temperatures applies for an interference-free operation of the Topvex SoftCooler:
• Outside air max. +33 °C
• Extract air max. +28 °C.
• Ambient temperature max. +28 °C.
When choosing the location it should be kept in mind that the unit requires maintenance regularly and that the inspec-
tion doors should be easily accessible. Leave free space for opening the doors and for taking out the main components
(figure 1). General maintenance includes among other things inspection and cleaning of the drip tray and flange coils.
A floor drain must be available in the room so that the condensation water can be drained off (chapter 6.7)
Avoid placing the appliance against a wall, as low frequency noise can cause vibrations in the wall even if the fan
noise-level is acceptable. If this is not possible it is recommended to carefully insulate the wall.
208767 | A006
Summary of Contents for Topvex TR 09 Series
Page 2: ...208767 A006...
Page 4: ......
Page 14: ...10 Installation A Fig 6 Illustration shows the left handed version of the unit 208767 A006...
Page 23: ...208767 A006...