4
4.2.2
Electrical data
Model
Voltage
Current (A)
Power (W)
Fuse, slow
Quantity of R410A, kg
Topvex SoftCooler TR09
400V 3N~, 50Hz
12
6090
16
4
Topvex SoftCooler TR12
400V 3N~, 50Hz
15
9230
20
4,4
Topvex SoftCooler TR15
400V 3N~, 50Hz
15
9230
20
5,5
4.3
Components
Fig. 2 Connections and basic components in left hand connected units
Position
Description
1
Compressor
2
Condenser coil
3
Evaporator coil
4
Filter drier with sight glass
5
Expansion valve
6
Drip-tray with drain
7
Water seal
8
Cable grommet for external cabling
9
El. cabinet with frequency converter
10
Exhaust air duct connection
11
Pressure/hot gas switches
12
Measuring points refrigerant system high/low
208767 | A006